 PROJECT: ADDITION 320 VALENCIA
 PERMIT#: 15011059
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE ON
 THE EXTERIOR OF THE DWELLING. WPB AMENDMENTS TO FBC 107
  
 2) REVISE THE RISER DIAGRAM TO INCLUDE THE SIZE OF THE
 MAIN DISCONNECT AND THE WIRE. WPB AMENDMENTS TO FBC 107
  
 3) PROVIDE CARBON MONOXIDE DETECTORS DUE TO THE GAS
 APPLIANCES AND PROVIDE OR VERIFY SMOKE AND CARBON
 MONOXIDE DETECTORS WHERE REQUIRED THROUGHOUT THE
 REMAINDER OF THE DWELLING. FBC-314 AND 315
  
 4) PROVIDE 3WAY LIGHT SWITCHING AND THE REQUIRED
 FIXTURE IN THE CORRIDOR CREATED BY THE RENNOVATION. NEC
 210.70 2(A)
  
 5) PROVIDE A SWITCHED LIGHT AT THE EXTERIOR DOOR ON THE
 SOUTH SIDE OF THE RENNOVATION OFF THE NEW MASTER SUITE.
 NEC 210.70.(B)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  