Plan Review Notes For Permit 15011059 |
Permit Number |
15011059 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-15 14:56:33 | 3/5/2015 | | PROJECT: ADDITION 320 VALENCIA | | PERMIT#: 15011059 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN | | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | FEE(S). | | | | 1) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE ON | | THE EXTERIOR OF THE DWELLING. WPB AMENDMENTS TO FBC 107 | | | | 2) REVISE THE RISER DIAGRAM TO INCLUDE THE SIZE OF THE | | MAIN DISCONNECT AND THE WIRE. WPB AMENDMENTS TO FBC 107 | | | | 3) PROVIDE CARBON MONOXIDE DETECTORS DUE TO THE GAS | | APPLIANCES AND PROVIDE OR VERIFY SMOKE AND CARBON | | MONOXIDE DETECTORS WHERE REQUIRED THROUGHOUT THE | | REMAINDER OF THE DWELLING. FBC-314 AND 315 | | | | 4) PROVIDE 3WAY LIGHT SWITCHING AND THE REQUIRED | | FIXTURE IN THE CORRIDOR CREATED BY THE RENNOVATION. NEC | | 210.70 2(A) | | | | 5) PROVIDE A SWITCHED LIGHT AT THE EXTERIOR DOOR ON THE | | SOUTH SIDE OF THE RENNOVATION OFF THE NEW MASTER SUITE. | | NEC 210.70.(B) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | | | | | |
|