Date |
Text |
2015-03-06 12:55:20 | RESIDENTIAL (R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) |
| FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| CODE. |
| |
| 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. SEC. 109.3 CITY AMENDMENTS TO FBC. VALUATION TO |
| INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S OVERHEAD AND |
| PROFIT AND THE DESIGN PROFESSIONAL FEES. VALUATION WAS |
| UPDATED TO $56,793 FOR THE ADDITION ALONE. NEED TO ADD |
| THE VALUE FOR ALL THE SCOPE OF WORK SHOWN ON SHEET A-2. |
| |
| 3- SHEET A-1: |
| A) NEW FIRST FLOOR PLAN IS MISSING ALL DIMENSIONS. SEC. |
| 107.2.1 CITY AMENDMENTS TO FBC. |
| |
| B) ROOF PLAN IS MISSING THE ROOF PITCH. SEC. R905.2.2 |
| OF 2010 FBC-RESIDENTIAL. |
| |
| 4- PROVIDE ROOF VENTILATION AS REQUIRED BY SEC. R806 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 5- PROVIDE ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| 2010 FBC-RESIDENTIAL. |
| |
| 6- SHEET S-3: |
| A) ACCORDING TO SEC. R301.2.1.4.3 OF 2010 |
| FBC-RESIDENTIAL THIS BUILDING IS LOCATED IN EXPOSURE |
| "C" NOT "B". REVISE AS REQUIRED. AND REVISE ALL THE |
| COMPONENTS AND CLADDING WIND DESIGN PRESSURES |
| ACCORDINGLY. |
| |
| B) REVISE THE ROOF LIVE LOAD (ATTIC LIVE LOAD) TO |
| COMPLY WITH TABLE R301.5 OF 2010 FBC-RESIDENTIAL. |
| |
| C) REVISE NOTE #1 OF COMPONENTS & CLADDING WIND |
| PRESSURES. ACCORDING TO FOOTNOTE ON FIGURE R301.2(7) OF |
| 2010 FBC-RESIDENTIAL. THE MIN. DIMENSION "A" IS 4'-0" |
| NOT "3'-0". REVISE AS REQUIRED. |
| |
| 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) NEW BATHROOM SINGLE HUNG WINDOW. |
| |
| B) HURRICANE SHUTTERS IF WINDOWS AND DOORS WITH GLAZING |
| DON'T HAVE IMPACT GLASS. AND PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. |
| |
| C) ROOF SHINGLES. |
| |
| D) METAL DOME VENTS AS SPECIFIED ON NOTE #1 ON SHEET |
| A-2. |
| |
| E) SELF ADHERING MODIFIED UNDERLAYMENT SPECIFIED ON |
| NOTE #1 ON SHEET A-2. |
| |
| F) EXTERIOR DOORS TO BE REPLACED AS SPECIFIED ON NOTE |
| #10 ON SHEET A-2. |
| |
| G) ALL WINDOWS TO BE REPLACED AS SPECIFIED ON NOTE#11 |
| ON SHEET A-2. |
| |
| H) WINDOW MULLIONS, IF WINDOWS ARE MULLED TOGETHER. |
| |
| I) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS, DETAILS AND NOTES. PROVIDE ONLY THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| SPECIFIED CONNECTOR. OR LIST FLORIDA PRODUCT APPROVAL |
| NUMBER (2010 FBC VERSION) NEXT TO THE SPECIFIED |
| CONNECTOR. |
| |
| J) PRE-CAST LINTELS AS SPECIFIED ON PLANS. |
| |
| 8- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 9- PROVIDE SKETCH SHOWING ALL WINDOWS TO BE REPLACED. |
| SPECIFY EXISTING TYPE AND SIZE OF WINDOWS AND TYPE AND |
| SIZE OF PROPOSED ONES TO VERIFY COMPLIANCE WITH THE |
| BEDROOM EGRESS REQUIREMENTS OF SEC. 604 OF 2010 |
| FBC-EXISTING BUILDING. CLEARLY IDENTIFY ALL ROOMS, |
| SPECIALLY ALL BEDROOMS. |
| |
| 10- DETAIL 2/S-2: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS SHOWING HOW THE EXISTING TRUSSES THAT |
| WILL BE CUT, WILL BE REINFORCED TO BE STRUCTURALLY |
| SOUND. SEC. R301 OF 2010 FBC-RESIDENTIAL. |
| |
| 11- SHEET S-1: REVISE NOTE #6.2: SEC. R803.2.3.1 OF |
| 2010 FBC-RESIDENTIAL REQUIRES 8D- RING SHANK NAILS. |
| CLEARLY SPECIFY RING SHANK NAILS FOR THE ROOF |
| SHEATHING. |
| |
| *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET. |
| SUBMITT OLD DRAWING FOR QUICK REFERENCE. |
| |