2015-03-06 13:26:36RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY
 SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- SHEET M-1:
 A) SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL NUMBER
 FROM THE EQUIPMENT SIZING CALCULATIONS REQUIRED BY
 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) MASTER BEDROOM TRANSFER GRILL SPECIFIED DOESN'T
 COMPLY WITH SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. ALL
 THE SUPPLY AIR INTO THE MASTER SUITE (INCLUDING
 BATHROOM AND CLOSET) NEED TO BE CONSIDERED WHEN SIZING
 THE TRANSFER GRILL.
  
  
 *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET.
 SUBMITT OLD DRAWING FOR QUICK REFERENCE.
  