Plan Review Notes For Permit 15011059 |
Permit Number |
15011059 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-03-06 13:26:36 | RESIDENTIAL (R3) ADDITION/ALTERATION MECHANICAL REVIEW | | COMMENTS. | | CODE: 2010 FBC. | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | 2- SHEET M-1: | | A) SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL NUMBER | | FROM THE EQUIPMENT SIZING CALCULATIONS REQUIRED BY | | 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | | B) MASTER BEDROOM TRANSFER GRILL SPECIFIED DOESN'T | | COMPLY WITH SEC. M1602.4 OF 2010 FBC-RESIDENTIAL. ALL | | THE SUPPLY AIR INTO THE MASTER SUITE (INCLUDING | | BATHROOM AND CLOSET) NEED TO BE CONSIDERED WHEN SIZING | | THE TRANSFER GRILL. | | | | | | *** PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH | | COMMENT TO EXPEDITE THE REVIEW PROCESS. | | *** PLEASE REPLACE AND REMOVE ANY REVISED SHEET. | | SUBMITT OLD DRAWING FOR QUICK REFERENCE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 |
|