2015-03-05 15:17:41 | 3/5/2015 |
| PROJECT: ADDITION 320 VALENCIA |
| PERMIT#: 15011059 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) PROVIDE A PANEL SCHEDULE INDICATING EXISTING |
| CIRCUITS AND NEW CIRCUITS REQUIRED FOR ADDITION. EVERY |
| CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| PURPOSE OR USE. NEC 408.4 |
| |
| 2) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN. WPB |
| AMENDMENTS TO FBC 107 |
| |
| 3) PROVIDE AND INDICATE ON THE FLOOR PLAN SMOKE |
| DETECTORS AS REQUIRED BY THE FBC-R 314 AND 315 AS |
| APPLICABLE. WHEN ALTERATIONS, REPAIRS, OR ADDITIONS |
| REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| INDIVIDUAL DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE |
| ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS. |
| FBC-RESIDENTIAL 314 AND 315. |
| |
| 4) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| THE ELECTRICAL PANEL ON THE FLOOR PLAN. WPB AMENDMENTS |
| TO FBC 107 |
| |
| 5) ADD RECEPTACLES ALONG WALL LINE OF NEW ADDITION AS |
| REQUIRED BY THE NEC 210.52. RECEPTACLES SHALL BE |
| INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| M (6 FT) FROM A RECEPTACLE OUTLET. |
| |
| 6) REVISE THE ELECTRICAL RISER DIGRAM TO INDICATE THE |
| SIZE OF THE PROPOSED OCPD FFEEDING NEW A/C |
| |
| 7) PROVIDE A SWITCHED LIGHT OUTLET IN THE BEDROOM. NEC |
| 210.70.210.70(1) |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |