2015-01-30 08:35:40PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C WITH
 A 170 MPH VULT WIND SPEED AND HAS A 22' MEAN ROOF
 HEIGHT. THE REQUIRED COMPONENT AND CLADDING NEGATIVE
 PRESSURE FOR THE FLAT ROOF IS -103 PSF FOR THE CORNERS
 (ROOF ZONE 3). THIS UPLIFT EXCEEDS THE MAXIMUM DESIGN
 PRESSURE OF -90 PSF FOR THE SYSTEM THAT YOU SELECTED
 FROM THE PRODUCT APPROVAL.