Plan Review Notes
Plan Review Notes For Permit 15011020
Permit Number 15011020
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-30 14:50:25WPB AMEND. TO 2010 FBC SEC.107.2.1.
 1) INDICATE ON THE PLAN THE TYPE OF PIPE MATERIAL TO BE
 INSTALLED.
 2) INDICATE ON THE PLAN THE SIZE OF THE PIPE TO BE
 INSTALLED.
 3) THE PLANS STATE THE DISTANCE FROM POINT A TO B IS 40
 FT. YET THE PIPE SECTIONS ADD UP TO 44 FT.WHICH MEANS
 THE 50 FT.ROW IS TO BE USED IN THE SIZING TABLE. SHOW
 THE CORRECT DEVELOPED LENGTH ON THE PLAN.
 4) CONSTRUCTION DOCUMENTS SHALL BE SUBMITTED IN TWO
 SETS.
 5) PLANS IN PENCIL ARE NOT ACCEPTABLE. MAKE COPIES OF
 THE PLANS ONCE ALL CORRECTIONS ARE MADE.
 6) THE PLANS SHOW THAT THIS IS A 1/2 PSI SYSTEM BUT THE
 SIZING TABLE REFERENCED ON THE PLAN IS FOR A 2 PSI.
 SYSTEM. CLARIFY.
 7) INDICATE ON THE PLAN IF THE 3" VENT IS NEW OR
 EXISTING. IF IT IS NEW, COMPLY WITH 2010 FBCR SEC. G
 2426 & G 2427 OF 2010 FBCR. IF NEW, SHOW THE VENT
 HEIGHT ABOVE THE ROOF, TYPE OF VENT, ETC.
 8) INDICATE THE SIZE OF THE APPLIANCE VENT ON THE PLAN.
 9) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR THE
 GAS APPLIANCE. THE APPLIANCE SHALL BE LISTED AND
 LABELED PER THE FBCR SEC.G2404.3.
 10) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER SEC.
 G2407 OF THE 2010 FBCR.
 11) THE APPLIANCE SHALL BE PROTECTED FROM PHYSICAL
 DAMAGE SINCE IT IS IN A GARAGE.
 12) THE REGULATOR SHALL BE VENTED TO THE EXTERIOR PER
 FBCR SEC.G2421.3.
 13) INDICATE ON THE PLAN THE TYPE OF APPLIANCE.THE
 APPLICATION NOTES" REPLACE OWNER'S WATER." I ASSUME
 THIS MEANS A WATER HEATER.INDICATE SUCH ON THE PERMIT
 APPLICATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  