2015-02-19 16:52:07 | 2/19/2015 |
| PROJECT: RIVERA |
| PERMIT#: 15010988 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) REVISE THE RISER DIAGRAM TO INDICATE A SINGLE |
| GROUNDING ELECTRODE CONDUCTOR SIZED IN ACCORDANCE WITH |
| NEC 250.66 TO ONE COMMON GROUNDING ELECTRODE SYSTEM. |
| NEC 250.66 |
| |
| 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING |
| INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED |
| FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO |
| ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE |
| DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR |
| STRUCTURES. NEC 250.94. |
| |
| 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE |
| LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND |
| SPECIFIC PURPOSE OR USE. NEC 408.4 |
| |
| 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 5) OCPD?S SHALL NOT BE LOCATED IN THE VICINITY OF |
| EASILY IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS. |
| NEC 240.24(B)(2)(D) |
| |
| 6) PROVIDE SPECS ON TANKLESS WATER HEATERS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |
| |