2015-02-05 10:18:18 | BUILDING PLAN REVIEW |
| PERMIT: 15010981 |
| ADD: 720 S. SAPODILLA AVE. # 510 |
| CONT: ABACOA CONSTRUCTION |
| TEL: (561) 633-8346 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 04/ 2015 |
| ACTION: DENIED |
| |
| 1) CONTRACTOR SUBMITTED CONTRACT VALUE FOR THE SCOPE OF |
| WORK. |
| |
| 2) AT MEET AND GREET STATION REVIEW NEW PROPOSED |
| FLOORING UNDER LAYMENT, THE COMPANY HAD A REPORT TO THE |
| WRONG STANDARD E-90, NOT THE E-492 FOR SOUND. |
| CONTRACTOR WILL LOOK FOR A NEW PRODUCT. NOTE THE |
| BUILDING HAS A 6 INCH CONCRETE SLAB, NOT A 8 INCH WHICH |
| MOST SOUND REPORTS USE WITH A DROPPED CEILING. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
2015-02-03 08:07:24 | BUILDING PLAN REVIEW |
| PERMIT: 15010981 |
| ADD: 720 S. SAPODILLA AVE. # 510 |
| CONT: ABACOA CONSTRUCTION |
| TEL: (561) 633-8346 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. FEB. 03/ 2015 |
| ACTION: DENIED |
| |
| THIS BUILDING WAS BUILT UNDER THE 1997 SSBC BUILDING |
| TYPE V-1HR= 2010 FBC-B TYPE IIIA |
| |
| 1) PLEASE PROVIDE WHAT TYPE OF FLOOR FINISH WILL BE |
| APPLIED OVER THIS TYPE OF FLOOR INSULATION. 2010 FBC-B |
| 804.1. |
| |
| 2) THE SUBMITTED SAM 3 90 SOUND CONTROL REPORT DOES NOT |
| INCLUDE ANY FLAME SPREAD NOR SMOKE DEVELOPMENT TESTING |
| RESULTS. PLEASE PROVIDE COMPLIANCE WITH: |
| 2010 FBC-B 719.2 CONCEALED INSTALLATION. INSULATING |
| MATERIALS, WHERE CONCEALED AS INSTALLED IN BUILDINGS OF |
| ANY TYPE OF CONSTRUCTION, SHALL HAVE A FLAME SPREAD |
| INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| OF NOT MORE THAN 450. WHERE A FLAME SPREAD INDEX OR A |
| SMOKE-DEVELOPED INDEX IS SPECIFIED IN THIS SECTION, |
| SUCH INDEX SHALL BE DETERMINED IN ACCORDANCE WITH ASTM |
| E 84 OR UL 723. |
| |
| 3) THE VALUATION IS FOR THE WHOLE JOB, NOT JUST THE |
| INSULATION, PLEASE PROVIDE A CONTRACT WITH THE TOTAL |
| CONTRACT VALUE OF THE PREJECT. |
| W P B ADMINISTRTIVE CODE 108.2 SCHEDULE OF PERMIT FEES. |
| ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL, |
| AND PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, |
| A FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| APPLICABLE GOVERNING AUTHORITY. |
| |
| 108.3* BUILDING PERMIT VALUATION. |
| IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFRENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS |
| FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| CONGRESS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |