2015-01-30 08:38:49THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE ACESS GATE IS INDICATED AS BEING15' AND IS NOT WIDE
 ENOUGH FOR FIRE LANE REQUIREMENTS AND FIRE APPARATUS
 USE. THE GATE SHALL BE 20' WIDE.
  
 A KNOX PADLOCK SHALL BE INSTALLED FOR ALL HOURS
 EMERGENCY VEHICLE ACCESS. FAILURE TO USE A KNOX PADLOCK
 WILL RESULT IN THE CHAIN LOCKING THE GATE BEING CUT AND
 THE PROPERTY UNSECURED.