2015-01-27 12:53:01RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- ENGINEER INFORMATION SUBMITTED IS INSUFFICIENT FOR
 PLAN REVIEW. INFORMATION SUBMITTED WAS A SINGLE PAGE
 WITH ONLY A SIMPSON HANGER TABLE. ENGINEER TO PROVIDE
 COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE
 SECOND FLOOR REPAIR FRAMING DETAILS, WALLS CONNECTIONS
 AND ROOF TO WALL CONNECTIONS AS REQUESTED BY THE
 BUILDING INSPECTOR ON 1/7/15 FIELD INSPECTION. SEC.
 107.2.1.3 OF CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR ALL THE SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED BY THE ENGINEER. PROVIDE PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER MAY LIST THE FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED CONNECTOR.
  
 3- ALL DOCUMENTS PREPARED BY AN ENGINEER NEED TO HAVE
 THE SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  