Plan Review Notes For Permit 15010890 |
Permit Number |
15010890 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-27 12:53:01 | RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS. | | CODE: 2010 FBC. | | | | 1- ENGINEER INFORMATION SUBMITTED IS INSUFFICIENT FOR | | PLAN REVIEW. INFORMATION SUBMITTED WAS A SINGLE PAGE | | WITH ONLY A SIMPSON HANGER TABLE. ENGINEER TO PROVIDE | | COMPLETE FRAMING DETAILS AND SPECIFICATIONS FOR THE | | SECOND FLOOR REPAIR FRAMING DETAILS, WALLS CONNECTIONS | | AND ROOF TO WALL CONNECTIONS AS REQUESTED BY THE | | BUILDING INSPECTOR ON 1/7/15 FIELD INSPECTION. SEC. | | 107.2.1.3 OF CITY AMENDMENTS TO FBC. | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | DCA RULE 9N-3 FOR ALL THE SIMPSON STRUCTURAL CONNECTORS | | SPECIFIED BY THE ENGINEER. PROVIDE PRODUCT APPROVAL | | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR | | ENGINEER MAY LIST THE FLORIDA PRODUCT APPROVAL NUMBER | | NEXT TO THE SPECIFIED CONNECTOR. | | | | 3- ALL DOCUMENTS PREPARED BY AN ENGINEER NEED TO HAVE | | THE SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 | | FLORIDA STATUTE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] | | | | |
|