2015-02-19 15:57:08 | 15010841 | | 401 CLEMATIS STREET | | EMERGENCY GAS GENERATOR | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | REVIEW COMMENTS. | | | | THE FEEDERS TO THE 1600 AMPERE DISCONNECT APPEAR TO BE | | UNDERSIZED. NEC 240.4(C) | | | | VERIFY THAT THE MAIN DISCONNECT FOR THE SEPERATELY | | DERIVED EMERGENCY SYSTEM IS LISTED AS SUITABLE FOR | | SERVICE EQUIPMENT. NEC 230.7 | | | | PROVIDE A DETAIL WHICH INDICATES THE MINIMUM SIZE WITH | | DEMINSIONS FOR THE LARGE JUNCTION BOXES/WIREWAYS | | REQUIRED FOR THE NEW FEEDERS. NEC 314.28 | | | | PROVIDE A DETAIL TO ANCHOR THE CONCRETE DUCT TO THE | | ROOF FOR THE WIND LOADING. FBC 1609 | | | | VERIFY THE LOAD ON THE NEW GENERATOR DOES NOT EXCEED | | ITS CAPACITY. NEC 702.5 | | | | THE ORANGE PHASE COLOR (SPECIFICATION IN SECTION 26 05 | | 53 ? 7) IS RESERVED FOR HIGH-LEG MARKING ON DELTA | | SYSTEMS. NEC 110.15 | | | | PROVIDE A GROUNDING DETAIL FOR THE EXISTING GROUNDING | | ELECTRODE SYSTEM INTERCONNECTIONS TO THE NEW GENERATOR | | AND SWITCHES. NEC 250.30 | | | | THE LINE DIAGRAM SHOWS A GENERATOR FEED TO A MANUAL | | TRANSFERE SWITCH FROM THE 1600 AMPERE EMERGENCY PANEL. | | IS THIS ACCURATE? NEC 210.15 | | | | INDICATE ON PLANS THE TYPE, LOCATION AND MATERIAL OF | | ALL REQUIRED ELECTRICAL SAFETY SIGNS/PLAQUES FOR | | LOCATION OF DISCONNECTS, FLASH PROTECTION, STAND BY | | GROUNDING POINT, ETC. SIGN MUST BE LEGIBLE, AND | | SUITABLE FOR THE LOCATION AND ENVIRONMENT. NEC 110.22, | | 110.9, 110.16, 702.8 | | | | | | ROBERT LECKY, CBO | | ELECTRICAL PLANS REVIEW | | 561-373-3701 | | [email protected] | | | | | | |
|