 401 CLEMATIS STREET
 EMERGENCY GAS GENERATOR
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 THE FEEDERS TO THE 1600 AMPERE DISCONNECT APPEAR TO BE
 UNDERSIZED. NEC 240.4(C)
  
 VERIFY THAT THE MAIN DISCONNECT FOR THE SEPERATELY
 DERIVED EMERGENCY SYSTEM IS LISTED AS SUITABLE FOR
 SERVICE EQUIPMENT. NEC 230.7
  
 PROVIDE A DETAIL WHICH INDICATES THE MINIMUM SIZE WITH
 DEMINSIONS FOR THE LARGE JUNCTION BOXES/WIREWAYS
 REQUIRED FOR THE NEW FEEDERS. NEC 314.28
  
 PROVIDE A DETAIL TO ANCHOR THE CONCRETE DUCT TO THE
 ROOF FOR THE WIND LOADING. FBC 1609
  
 VERIFY THE LOAD ON THE NEW GENERATOR DOES NOT EXCEED
 ITS CAPACITY. NEC 702.5
  
 THE ORANGE PHASE COLOR (SPECIFICATION IN SECTION 26 05
 53 ? 7) IS RESERVED FOR HIGH-LEG MARKING ON DELTA
 SYSTEMS. NEC 110.15
  
 PROVIDE A GROUNDING DETAIL FOR THE EXISTING GROUNDING
 ELECTRODE SYSTEM INTERCONNECTIONS TO THE NEW GENERATOR
 AND SWITCHES. NEC 250.30
  
 THE LINE DIAGRAM SHOWS A GENERATOR FEED TO A MANUAL
 TRANSFERE SWITCH FROM THE 1600 AMPERE EMERGENCY PANEL.
 IS THIS ACCURATE? NEC 210.15
  
 INDICATE ON PLANS THE TYPE, LOCATION AND MATERIAL OF
 ALL REQUIRED ELECTRICAL SAFETY SIGNS/PLAQUES FOR
 LOCATION OF DISCONNECTS, FLASH PROTECTION, STAND BY
 GROUNDING POINT, ETC. SIGN MUST BE LEGIBLE, AND
 SUITABLE FOR THE LOCATION AND ENVIRONMENT. NEC 110.22,
 110.9, 110.16, 702.8
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  
  