2015-01-24 11:31:01BUILDING PLAN REVIEW
 PERMIT: 15010823
 ADD: 1220 LONGWOOD ST
 CONT: MASIMO CONSTRUCTION
 TEL: (561)445-5427
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 24/ 2015
 ACTION: BUILDING PROVISO
  
 1) ROOF SLOPE NOT PROVIDED:
 2010 FBC-RESIDENTIAL
 R905.2.6.1 WIND RESISTANCE OF ASPHALT SHINGLES.
 R905.2.7 UNDERLAYMENT APPLICATION.
 FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS
 HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS
 VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE), TWO
 LAYERS OF UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I
 OR TYPE II, ASTM D 4869 TYPE I OR TYPE II, OR ASTM D
 6757 SHALL BE APPLIED IN THE FOLLOWING MANNER:
 1. APPLY A MINIMUM 19-INCH-WIDE (483 MM) STRIP OF
 UNDERLAYMENT FELT PARALLEL WITH AND STARTING AT THE
 EAVES.
 2. STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM)
 SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19
 INCHES (483 MM). DISTORTIONS IN THE UNDERLAYMENT SHALL
 NOT INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL.
 3. END LAPS SHALL BE OFFSET BY 6 FEET (1829 MM).
 4. CORROSION RESISTANT FASTENERS ARE TO BE APPLIED
 ALONG THE OVERLAP AT A MAXIMUM SPACING OF 36 INCHES
 (914 MM) ON CENTER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676