Plan Review Notes
Plan Review Notes For Permit 15010822
Permit Number 15010822
Review Stop E
Sequence Number 2
Notes
Date Text
2015-03-06 13:40:501) NO WINDLOAD CALCULATIONS HAVE BEEN INCLUDED I THE
 SUBMITTAL. PROVIDE WIND LOAD CALCULATIONS THAT INCLUDE
 THE LUMINAIRE AND CAMERA INSTALLATION. WPB AMENDMENTS
 TO THE FBC 107
  
 2) REVISE THE GROUNDING DETAIL FOR THE BROOKS PULL BOX
 AND THE LIGHT POLES ON SHEET E-2 TO INDICATE THE
 EQUIPMENT GROUNDING CONDUCTOR CONNECTING TO THE DRIVEN
 GROUND ROD. NEC 250.32
  
 3) REVISE THE DETAILS FOR THE POLES THAT ARE PROPOSED
 TO SHARE THE LOW VOLTAGE CAMERA WIRING WITH THE HIGH
 VOLTAGE LIGHTING WIRING.
 A) THE LIGHTH POLE DETAIL INDICATES A 1" PVC WITH
 WIRING FOR LIGHTING ONLY, PLEASE CLARIFY. ARE THERE
 CAMERAS INSTALLED ON THESE POLES?
 B) THE SECURITY CAMERA DETAIL INDICATES AN ALUMINUM
 CONDUIT FOR THE CAMERAS BUT ALSO INDICATES IN THE TITLE
 OF THE DETAIL THESE POLES SHARE THE CIRCUITRY FOR THE
 LIGHTING BUT DOES NOT INDICATE ANY DETAIL AS TO HOW.
 C) THE 5FT SECURITY CAMERA POLE DETAIL INDICATES A 1"
 PVC WITH PULL BOX AND NOTES THAT THERE IS A 120V GFI
 MOUNTED INSIDE A STAINLESS STEEL CAMERA CABINET BUT
 AGAIN DOES NOT INDICATE HOW THE POWER AND LIGHTING
 CIRCUITRY ARE PROPOSED TO BE INSTALLED.
 THERE IS NO MENTION OF THE ROUTING OR INSTALLATION OF
 THE SPECIFIC WIRING METHODS AND HOW THEY WILL BE
 SEPARARTED OR HOW THE BONDING AND GROUNDING WILL BE
 ACCOMPLISHED. ALL THREE OF THESE DETAILS NEED TO BE
 REVISED TO SHOW MORE DETAIL THE INSTALLATION AND
 SEPARATION OF SYSTEMS WIRING AND THE GROUNDING AND
 BONDING IN ACCORDANCE WITH THE NEC.
  
 4) PROVIDE MANUFACTURER PRODUCT APPROVALS ON ALL CAMERA
 AND RELATED EQUIPMENT SUCH AS POWER SUPPLIES, STAINLESS
 STEEL ENCLOSURES AND THE CAMERAS THEMSELVES.
  
 5) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY. SUITABILITY FOR
 INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS
 OF THIS CODE. INDICATE ON THE PLAN AND PROVIDE A
 SUBMITTALE OF THE FIBER OPTIC CABLE PROPOSED TO BE
 INSTALLED IN AN UNDERGROUND RACEWAY. NEC 110.3(B)
  
 6) INDICATE HOW THE PROPOSED EXTERIOR LIGHTING IS
 INTENDED TO COMPLY WITH THE FBC-ENERGY SECTION 505.2.4
 EXTERIOR LIGHTING CONTROLS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]