Plan Review Notes
Plan Review Notes For Permit 15010786
Permit Number 15010786
Review Stop B
Sequence Number 2
Notes
Date Text
2015-01-23 07:40:502ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 ITEMS 1 AND 2 FROM 1ST REVIEW HAVE BEEN ADDRESSED.
  
 3) ACCORDING TO THE PBC PROPERTY APPRAISER THIS
 STRUCTURE WAS BUILT IN 1985 AND HAS A VALUE OF
 $504,099.00. THE WINDLOAD REQUIREMENTS WERE NOT ADOPTED
 IN PALM BEACH COUNTY UNTIL 1988. THEREFORE, YOU ARE
 REQUIRED TO SHOW COMPLIANCE WITH THE FOLLOWING:
 FBC EXISTING BUILDINGS 611.8
 WHEN A ROOF COVERING ON AN EXISTING
 SITE-BUILT-SINGLE-FAMILY RESIDENTIAL STRUCTURE IS
 REMOVED AND REPLACED ON A BUILDING THAT IS LOCATED IN
 THE WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA
 BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE
 OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR
 FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT
 PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR
 PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE:
  
 (A) ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS
 REQUIRED BY SECTION 611.8.1
  
 (B) MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION
 SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN
 THE COST OF RE-ROOFING.
  
 EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES
 PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT
 REQUIRED TO COMPLY WITH THIS SECTION.
  
 FBC EXISTING BUILDINGS 611.8.1 ROOF-TO-WALL CONNECTIONS
 FOR SITE-BUILT SINGLE-FAMILY RESIDENTIAL STRUCTURES.
 WHERE REQUIRED BY SECTION 611.8, THE INTERSECTION OF
 ROOF FRAMING WITH THE WALL BELOW SHALL PROVIDE
 SUFFICIENT RESISTANCE TO MEET THE UPLIFT LOADS
 SPECIFIED IN TABLE 611.8.1 EITHER BECAUSE OF EXISTING
 CONDITIONS OR THROUGH RETROFIT MEASURES. AS AN
 ALTERNATIVE TO AN ENGINEERED DESIGN, THE PRESCRIPTIVE
 RETROFIT SOLUTIONS PROVIDED IN SECTIONS 611.8.1.1
 THROUGH 611.8.1.7 SHALL BE ACCEPTED AS MEETING THE
 MANDATED ROOF-TO-WALL RETROFIT REQUIREMENTS.
  
 EXCEPTIONS:
  
 1. WHERE IT CAN BE DEMONSTRATED (BY CODE ADOPTION DATE
 DOCUMENTATION AND PERMIT ISSUANCE DATE) THAT
 ROOF-TO-WALL CONNECTIONS AND/OR ROOF-TO-FOUNDATION
 CONTINUOUS LOAD PATH REQUIREMENTS WERE REQUIRED AT THE
 TIME OF ORIGINAL CONSTRUCTION.
  
 2. ROOF-TO-WALL CONNECTIONS SHALL NOT BE REQUIRED
 UNLESS EVALUATION AND INSTALLATION OF CONNECTIONS AT
 GABLE ENDS OR ALL CORNERS CAN BE COMPLETED FOR 15
 PERCENT OF THE COST OF ROOF REPLACEMENT.
  
  
  