2015-06-02 13:29:49 | 6/2/2015 |
| PROJECT: INTERIOR REMODEL |
| PERMIT#: 14071125 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 3RD ELECTRICAL PLAN REVIEW OF REVISION #15010691 |
| ACTION: DENIED |
| |
| REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| COMMENTS: |
| |
| 1) PERMEANT PLAQUES ARE REQUIRED AT THE SERVICE |
| ENTRANCE AND PANEL LOCATIONS TO IDENTIFY THE MEANS OF |
| DISCONNECT(S) REQUIRED TO DISCONNECT ALL UNGROUNDED |
| CONDUCTORS SUPPLYING THE NEWLY CREATED SPACE. WHERE A |
| BUILDING OR STRUCTURE HAS ANY COMBINATION OF FEEDERS, |
| BRANCH CIRCUITS, OR SERVICES PASSING THROUGH IT OR |
| SUPPLYING IT, A PERMANENT PLAQUE OR DIRECTORY SHALL BE |
| INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT DISCONNECT |
| LOCATION DENOTING ALL OTHER SERVICES, FEEDERS, OR |
| BRANCH CIRCUITS SUPPLYING THAT BUILDING OR STRUCTURE OR |
| PASSING THROUGH THAT BUILDING OR STRUCTURE AND THE AREA |
| SERVED BY EACH. NEC 225.37 SEE ALSO NEC 230.2(E) |
| |
| 2) PROVIDE PANEL SCHEDULE(S) INDICATING ALL LIGHTING |
| AND POWER OUTLET CIRCUITS. EVERY CIRCUIT AND CIRCUIT |
| MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS |
| CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 |
| |
| 3) IDENTIFY THE CIRCUITS FEEDING THE EMERGENCY AND EXIT |
| LIGHTING ON THE FLOOR PLAN IN COMPLIANCE WITH THE NEC |
| 700.12. THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT |
| SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE |
| NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY |
| LOCAL SWITCHES. NEC 700.12(F) |
| |
| 4) THIS IS A REVISION TO EXISTING PERMIT AND PLAN. THE |
| DESIGN PROFESSIONAL RESPONSIBLE IS JOHN HOLT PE OF |
| WELLINGTON. WHILE YOU MAY PROVIDE INFORMATION IN THE |
| WAY OF "MARKED UP" OR "RED LINED" PLANS TO THE DESIGN |
| PROFESSIONAL, ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC, WPB |
| AMENDMENTS 107.2.1 |
| 4B) ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, |
| OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND |
| BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS |
| PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE |
| SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH |
| SAID SEAL. FL SS 471.025 668.001-668.006. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |