Plan Review Notes
Plan Review Notes For Permit 15010651
Permit Number 15010651
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2015-06-26 15:16:31THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THIS REVIEW APPROVAL IS FOR THE FOUNDATION ONLY.
  
 THE REQUIREMENT OF A FULL SPRINKLER SYSTEM ON ALL
 FLOORS REMIANS UNDER REVIEW AND IS NOT APPROVED UNDER
 THIS PERMIT.
  
 THE LIFE SAFETY GENERAL INFORMATION ON SHEET AS000 HAS
 NOT BEEN FULLY REVIEWED AND/OR APPROVED BY FIRE
 PREVENTION REGARDING "OPEN" OR "CLOSED" EXTERIOR WALL
 OPENINGS. GREATER DETAIL AND EXPLANATION IS NEEDED FOR
 THE EXTERIOR WALL COVERINGS AND THEIR COMPLIANCE WITH
 THE REQUIREMENTS OF THE FLORIDA LIFE SAFETY CODE, NFPA
 101 CHAPTER 42, NFPA 88A AND IT'S A HIGHRISE BUILDING.
  
 PER NFPA 88A -
 5.5 OPENING REQUIREMENTS FOR OPEN PARKING STRUCTURES.
 5.5.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS OPEN
 TO THE
 ATMOSPHERE, FOR AN AREA OF NOT LESS THAN 0.4 M2 FOR
 EACH LINEAR
 METER (1.4 FT2 FOR EACH LINEAR FOOT) OF ITS EXTERIOR
 PERIMETER.
  
 PROVIDE DETAILS THAT THE PROPOSED DESIGN ON EACH TEIR
 COMPLIES BEFORE AND THEN AFTER THE FACADE IS APPLIED.
  
 5.5.2 SUCH OPENINGS SHALL BE DISTRIBUTED OVER 40
 PERCENT OF
 THE BUILDING PERIMETER OR UNIFORMLY OVER TWO OPPOSING
 SIDES.
  
 PROVIDE DEATILS THAT THE PROPOSED DESIGN ON EACH WALL
 BEFORE AND THEN AFTER THE FACADE IS APPLIED.
2015-06-15 14:27:00NEW DRAWINGS SUBMITTED. JG.