2015-05-22 11:02:051. PLEASE CONNECT THE FIRE RISER DRAIN TO THE SANITARY
 SYSTEM RATHER THAN THE STORMWATER SYSTEM. PER NFPA
 STANDARDS: WHERE IT IS NOT POSSIBLE TO DISCHARGE
 OUTSIDE OF THE BUILDING WALL, THE DRAIN SHOULD BE PIPED
 TO A SUMP, WHICH IN TURN SHOULD DISCHARGE BY GRAVITY OR
 BE PUMPED TO A WASTE WATER DRAIN OR SEWER.
  
 2. VERIFY THAT THE PEAK FLOWS FROM THE VARIOUS SUMP
 PUMPS (DRAINAGE AND SEWER) HAVE BEEN INCLUDED IN THE
 SANITARY SEWER AND STORMWATER DESIGN CALCULATIONS FROM
 THE SITE.
  