2015-06-02 11:27:17 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| EOR: THOMAS ROGERS, PE (ONM&J) |
| ARCHITECT: WILLIAM A. HANSER (LEO A DALY) |
| |
| 1. THRESHOLD INSPECTION PLAN IS ACCEPTABLE WITH THE |
| FOLLOWING EXCEPTION. |
| ALTHOUGH LIKELY NOT APPLICABLE TO THIS PROJECT, PLEASE |
| SEE PAGE 10 ITEMS B AND C, AND FBC 1609.1.2(2); ALL |
| OPENINGS ARE TO MEET THE REQUIREMENTS FOR MISSILE |
| IMPACT RESISTANCE (REVISE LANGUAGE TO REMOVE REFERENCE |
| TO THE 60 FEET LIMITATION). |
| |
| 2. INFORMATIONAL ONLY - AS THIS IS A THRESHOLD JOB, |
| THREE SETS OF ALL DOCUMENTS REQUIRED. |
| |
| 3-7. OK |
| |
| 8A. FBC 705.8, PREVIOUS COMMENT WAS PARTIALLY |
| ADDRESSED. THE DIMENSION FROM THE PROPOSED GARAGE TO |
| ASSUMED PROPERTY LINE HAS BEEN PROVIDED ON THE PLAN AS |
| 30FT. SEE FBC 705.3: |
| |
| WHERE A NEW BUILDING IS TO BE ERECTED ON THE SAME LOT |
| AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED |
| IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING |
| SHALL BE SUCH THAT THE EXTERIOR WALL AND THE OPENING |
| PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA |
| AS SET FOR THE IN SECTIONS 705.5 AND 705.8. |
| |
| REVISE THE PLAN TO SHOW COMPLIANCE FOR THE EXISTING |
| BUILDING (APPEARS TO BE 12 FT FROM THE ASSUMED PROPERTY |
| LINE). THIS APPLIES ONLY TO THE PORTIONS OF THE |
| BUILDINGS WHICH DIRECTLY FACE THE OTHER BUILDING. |
| |
| IF ASSUMED PROPERTY LINE IS RELOCATED, SHOW COMPLIANCE |
| FOR EACH BUILDING AS APPLICABLE (FBC 705.5 AND 705.8). |
| |
| 9-11. OK |
| |
| 12. DELEGATED ENGINEERING (HAYWARD BAKER) TO BE |
| REVIEWED BY ENGINEER OF RECORD, FBC 107. |
| |
| THIS MAY BE DONE BY INCORPORATING A REFERENCE INTO THE |
| PLAN (AS WAS DONE WITH THE SOILS REPORT), A SHOP |
| DRAWING REVIEW STAMP, OR A LETTER. OTHER METHODS WOULD |
| BE CONSIDERED. |
| |
| HB2 AND HB3 ARE NOT SIGNED AND SEALED; PLEASE SEE FBC |
| 471, FAC61G15-23.002 (DOC UMENTS PREPARED BY AN |
| ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE |
| SIGNED, SEALED, DATED ORIGINALS). PLEASE FEEL FREE TO |
| CONTACT ME TO DISCUSS IF ENGINEER OBJECTS TO SIGNING |
| AND SEALING THESE SHEETS. |
| |
| 13. OK |
| |
| 14. PER CONVERSATION WITH ENGINEER, PLEASE REVISE S9.1 |
| SECTION 1, TO SHOW CONTINUOUS WATERPROOFING AT THE |
| FOOTING, FBC 1805.3.3. |
| |
| WATERPROOFING DETAILS (PER ENGINEERING DETAILS ARE TO |
| BE FOUND ON ARCHITECTURAL SHEETS) WERE NOT SUBMITTED. |
| PLEASE PROVIDE WATERPROOFING DETAILS FOR THIS PHASE. |
| |
| PLEASE BE ADVISED THAT, IF SPEC SHEETS FOR THE |
| WATERPROOFING PRODUCTS ARE NOT PROVIDED PRIOR TO PERMIT |
| ISSUANCE, THEY WILL BE REQUIRED TO BE SUBMITTED PRIOR |
| TO INSTALLATION. CONTRACTOR OR DESIGNER IS ENCOURAGED |
| TO SUBMIT AT THIS TIME TO AVOID FIELD DELAYS. |
| |
| ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD |
| PRIOR TO SUBMITTAL TO THE BUILDING DIVISION. |
| |
| 15. OK |
| |
| 16. ADVISORY ONLY - CONSTRUCTION HOURS ARE 7AM - 7PM |
| MONDAY THROUGH FRIDAY; 8AM - 8PM WEEKENDS, CITY OF WEST |
| PALM BEACH MUNICIPAL CODE SECTION 34-72. A WRITTEN |
| EXCEPTION MAY BE GRANTED BY THE BUILDING OFFICIAL; |
| PLEASE SUBMIT ANY SUCH REQUESTS (IF NEEDED) TIMELY TO |
| [email protected], CC [email protected] AND [email protected]. |
| |
| 17. OK |
| |
| NEW COMMENT: |
| |
| 18. PER CONTRACTOR, NO ELECTRICAL WORK IS A PART OF |
| THIS PHASE. BE ADVISED THAT, PRIOR TO FIRST POUR, THE |
| BUILDING INSPECTOR WILL REQUIRE INFORMATION FROM THE |
| ELECTRICAL ENGINEER OR ARCHITECT WHICH VERIFIES THAT |
| BUILDING GROUNDING IS NOT A PART OF THIS PHASE. IN |
| ORDER TO AVOID FIELD DELAYS, DESIGNER IS ENCOURAGED TO |
| SUBMIT THIS INFORMATION AT THIS TIME. |
| |
| |