2015-06-02 11:27:17****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
 EOR: THOMAS ROGERS, PE (ONM&J)
 ARCHITECT: WILLIAM A. HANSER (LEO A DALY)
  
 1. THRESHOLD INSPECTION PLAN IS ACCEPTABLE WITH THE
 FOLLOWING EXCEPTION.
 ALTHOUGH LIKELY NOT APPLICABLE TO THIS PROJECT, PLEASE
 SEE PAGE 10 ITEMS B AND C, AND FBC 1609.1.2(2); ALL
 OPENINGS ARE TO MEET THE REQUIREMENTS FOR MISSILE
 IMPACT RESISTANCE (REVISE LANGUAGE TO REMOVE REFERENCE
 TO THE 60 FEET LIMITATION).
  
 2. INFORMATIONAL ONLY - AS THIS IS A THRESHOLD JOB,
 THREE SETS OF ALL DOCUMENTS REQUIRED.
  
 3-7. OK
  
 8A. FBC 705.8, PREVIOUS COMMENT WAS PARTIALLY
 ADDRESSED. THE DIMENSION FROM THE PROPOSED GARAGE TO
 ASSUMED PROPERTY LINE HAS BEEN PROVIDED ON THE PLAN AS
 30FT. SEE FBC 705.3:
  
 WHERE A NEW BUILDING IS TO BE ERECTED ON THE SAME LOT
 AS AN EXISTING BUILDING, THE LOCATION OF THE ASSUMED
 IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING
 SHALL BE SUCH THAT THE EXTERIOR WALL AND THE OPENING
 PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA
 AS SET FOR THE IN SECTIONS 705.5 AND 705.8.
  
 REVISE THE PLAN TO SHOW COMPLIANCE FOR THE EXISTING
 BUILDING (APPEARS TO BE 12 FT FROM THE ASSUMED PROPERTY
 LINE). THIS APPLIES ONLY TO THE PORTIONS OF THE
 BUILDINGS WHICH DIRECTLY FACE THE OTHER BUILDING.
  
 IF ASSUMED PROPERTY LINE IS RELOCATED, SHOW COMPLIANCE
 FOR EACH BUILDING AS APPLICABLE (FBC 705.5 AND 705.8).
  
 9-11. OK
  
 12. DELEGATED ENGINEERING (HAYWARD BAKER) TO BE
 REVIEWED BY ENGINEER OF RECORD, FBC 107.
  
 THIS MAY BE DONE BY INCORPORATING A REFERENCE INTO THE
 PLAN (AS WAS DONE WITH THE SOILS REPORT), A SHOP
 DRAWING REVIEW STAMP, OR A LETTER. OTHER METHODS WOULD
 BE CONSIDERED.
  
 HB2 AND HB3 ARE NOT SIGNED AND SEALED; PLEASE SEE FBC
 471, FAC61G15-23.002 (DOC UMENTS PREPARED BY AN
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS). PLEASE FEEL FREE TO
 CONTACT ME TO DISCUSS IF ENGINEER OBJECTS TO SIGNING
 AND SEALING THESE SHEETS.
  
 13. OK
  
 14. PER CONVERSATION WITH ENGINEER, PLEASE REVISE S9.1
 SECTION 1, TO SHOW CONTINUOUS WATERPROOFING AT THE
 FOOTING, FBC 1805.3.3.
  
 WATERPROOFING DETAILS (PER ENGINEERING DETAILS ARE TO
 BE FOUND ON ARCHITECTURAL SHEETS) WERE NOT SUBMITTED.
 PLEASE PROVIDE WATERPROOFING DETAILS FOR THIS PHASE.
  
 PLEASE BE ADVISED THAT, IF SPEC SHEETS FOR THE
 WATERPROOFING PRODUCTS ARE NOT PROVIDED PRIOR TO PERMIT
 ISSUANCE, THEY WILL BE REQUIRED TO BE SUBMITTED PRIOR
 TO INSTALLATION. CONTRACTOR OR DESIGNER IS ENCOURAGED
 TO SUBMIT AT THIS TIME TO AVOID FIELD DELAYS.
  
 ALL SUBMITTALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE BUILDING DIVISION.
  
 15. OK
  
 16. ADVISORY ONLY - CONSTRUCTION HOURS ARE 7AM - 7PM
 MONDAY THROUGH FRIDAY; 8AM - 8PM WEEKENDS, CITY OF WEST
 PALM BEACH MUNICIPAL CODE SECTION 34-72. A WRITTEN
 EXCEPTION MAY BE GRANTED BY THE BUILDING OFFICIAL;
 PLEASE SUBMIT ANY SUCH REQUESTS (IF NEEDED) TIMELY TO
 [email protected], CC [email protected] AND [email protected].
  
 17. OK
  
 NEW COMMENT:
  
 18. PER CONTRACTOR, NO ELECTRICAL WORK IS A PART OF
 THIS PHASE. BE ADVISED THAT, PRIOR TO FIRST POUR, THE
 BUILDING INSPECTOR WILL REQUIRE INFORMATION FROM THE
 ELECTRICAL ENGINEER OR ARCHITECT WHICH VERIFIES THAT
 BUILDING GROUNDING IS NOT A PART OF THIS PHASE. IN
 ORDER TO AVOID FIELD DELAYS, DESIGNER IS ENCOURAGED TO
 SUBMIT THIS INFORMATION AT THIS TIME.
  
  