Plan Review Notes
Plan Review Notes For Permit 15010651
Permit Number 15010651
Review Stop P
Sequence Number 2
Notes
Date Text
2015-04-23 11:01:291) SHT.F-PP 402 SHOWS SUMP PUMPS IN THE ELEVATOR
 SHAFTS. THE SUMP PUMPS SHALL BE INDIRECTLY CONNECTED TO
 THE PLUMBING SYSTEM PER THE 2010 FPC SEC. 301.6 AND
 COMPLY WITH SECTION 1003.4.
 2) SUBMIT A DETAIL AND SIZING CALCULATIONS FOR THE OIL
 SEPARATOR.COMPLY WITH 2010 FPC SEC. 1004.4.2.1.
 3) SHT. F-PP110 REFERS TO SHT.F-PP401. THERE IS NO SUCH
 SHEET IN THIS SET OF PLANS. CLARIFY.
 4) SUBMIT DETAILS ON THE PUMPS IN THE ELEVATOR SHAFTS,
 THE STORM DRAIMAGE AN`D THE SEWAGE PUMPS. WPB AMEND.TO
 2010 FBC SEC. 107.2.1.
 5) THERE IS AN 8" STORM DRAIN NEAR GRID LINE D2 THAT IS
 SHOWN ON F-PP402 BUT IS NOT SHOWN ON PLAN. CLARIFY.
 6) SHT. F-PP110 A - AS DRAWN, IT APPEARS THAT THE PUMP
 DISCHARGE FROM THE ELEVATOR SUMPS ARE PUMPING AGAINST
 EACH OTHER. CLARIFY.
 7) SUBMIT A SEPARATE RISER FOR THE UNDERGROUND
 CONDENSATE AND FOR THE SANITARY. THE PIPING ON SHT.
 F-PP402 IS CRAMMED SO CLOSE TOGETHER IT IS ALMOST
 IMPOSSIBLE TO REVIEW. EXPAND THE PIPING DIAGRAM SO A
 COMPREHENSIVE REVIEW CAN BE PEFORMED. DO THE SAME FOR
 THE SANITARY PIPING ALSO.
 WPB AMEND.TO 2010 FBC SEC. 107.2.1.
 8) SHOW THE LOCATION OF THE OIL INTERCEPTOR ON THE PLAN
 VIEW DRAWING. WPB AMEND.TO 2010 FBC SEC. 107.2.1.
  