Plan Review Notes For Permit 15010651 |
Permit Number |
15010651 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-04-13 16:43:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THIS REVIEW APPROVAL IS FOR THE FOUNDATION ONLY. | | | | THE REQUIREMENT OF A FULL SPRINKLER SYSTEM ON ALL | | FLOORS REMIANS UNDER REVIEW AND IS NOT APPROVED UNDER | | THIS PERMIT. | | | | THE LIFE SAFETY GENERAL INFORMATION ON SHEET AS000 HAS | | NOT BEEN FULLY REVIEWED AND/OR APPROVED BY FIRE | | PREVENTION REGARDING "OPEN" OR "CLOSED" EXTERIOR WALL | | OPENINGS. GREATER DETAIL IS NEEDED FOR THE EXTERIOR | | WALL COVERINGS AND THEIR COMPLIANCE WITH THE | | REQUIREMENTS OF THE FLORIDA LIFE SAFETY CODE, NFPA 101 | | CHAPTER 42, NFPA 88A AND IT'S A HIGHRISE BUILDING. |
|