2015-05-01 17:06:17****CORRECTIONS****
 ****REVISED 5/14/15***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
 EOR: THOMAS ROGERS, PE (ONM&J)
 ARCHITECT: WILLIAM A. HANSER (LEO A DALY)
  
 1. INFORMATIONAL ONLY - A COPY OF THE THRESHOLD
 INSPECTION PLAN PREPARED BY THOMAS J. ROGERS, PE,
 ONM&J, HAS BEEN ROUTED TO KEN CONRAD, CHIEF BUILDING
 INSPECTOR.
  
 2. INFORMATIONAL ONLY - AS THIS IS A THRESHOLD JOB,
 THREE SETS OF ALL DOCUMENTS REQUIRED.
  
 3. NA
  
 4. THRESHOLD DOCUMENTS PENDING K. CONRAD APPROVAL.
  
 PLEASE PROVIDE A RESUME FOR THE SUPERINTENDENT. **
  
 5. THE SOILS PROVIDED IS NOT AN ORIGINAL. ORIGINAL
 SIGNED, SEALED REPORTS ARE REQUIRED, FS471.
  
 THE SOILS HAS BEEN REVISED SINCE THE ENGINEER'S REVIEW
 (REFERENCE ON SHEET S7.1). PRIOR TO RESUBMITTAL, THE
 EOR IS TO REVIEW ALL SUBMITTALS INCLUDING THE
 GEOTECHNICAL REPORT, FBC 107.
  
 **
  
 6-7. OK
  
 8A. FBC 705.8, SHOW LOCATION OF ASSUMED PROPERTY LINE
 (BETWEEN THE EXISTING CONVENTION CENTER AND PROPOSED
 PARKING GARAGE); PLEASE REVISE PLAN TO SHOW DISTANCE OF
 EACH BUILDING TO THE ASSUMED PROPERTY LINE (FBC 705.3)
  
 2ND REVIEW; THIS WAS NOT PROVIDED. ARE THE TWO
 BUILDINGS TO BE CONSIDERED ONE LARGE BUILDING? IF THEY
 ARE TO BE CONSIDERED ONE BUILDING, PLEASE PROVIDE
 INFORMATION SHOWING COMPLIANCE WITH FBC TABLE 501. IF
 THEY ARE TWO BUILDINGS, ENOUGH INFORMATION FOR EACH
 BUILDING IS TO BE PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH FBC 705.3.
  
 PROVIDE THE AREA OF THE PROPOSED GARAGE, FBC TABLE 501.
  
 8B, SHEET AS000 INCLUDES ?MIXED USE OCCUPANCY HOUSING
 A?; PLEASE CLARIFY. SEE FBC CHAPTER 3.
  
 8C, SHEET AS000 CITES SECTION 905.3 EXCEPTIONS 3 & 4
 FOR SPRINKLERS; THIS SECTION IS FOR STANDPIPE
 REQUIREMENTS. PLEASE REVISE OR CLARIFY.
  
 ADVISORY ONLY; SPRINKLERS MAY BE REQUIRED FOR THE ROOF
 TOP CANOPY PER DISCUSSIONS WITH FIRE DEPT. THIS IS NOT
 REQUIRED TO BE ADDRESSED AT THIS TIME.
  
 9-11. OK
  
 NEW COMMENTS:
  
 12. EMAIL FROM CONTRACTOR WHICH CLARIFIES SCOPE UNDER
 THIS PERMIT STATES THAT A TEMPORARY SHEET PILE WILL BE
 INSTALLED. THIS IS SHOWN ON THE VIBROFLOTATION SITE
 PLAN BUT IS NOT SHOWN ANYWHERE IN THE PLAN PROVIDED.
 PROVIDE ALL INFORMATION REQUIRED TO INCORPORATE THE
 TEMPORARY SHEET PILES INTO THE SCOPE OF THIS PERMIT,
 FBC 107.
  
 13. OK
  
 14. PRIOR TO RESUBMITTING, PLEASE VERIFY THAT PLANS ARE
 COMPLETE. FOR INSTANCE; SHEETS S1A AND S2A REFER TO
 DETAIL 7 ON S9.3, BUT THAT SHEET WAS NOT PROVIDED (SEE
 S2A AT GRIDLINE A13). DETAIL 8 S9.1 LACKS THE STIRRUP
 SIZE.
  
 THE TRENCH DETAIL WAS PROVIDED, S9.1 SECTION 1, BUT THE
 WATERPROOFING INFORMATION WAS NOT PROVIDED (REFERS TO
 ARCHITECTURAL SHEETS, WHICH WERE NOT PROVIDED). ALSO
 PLEASE NOTE THAT THIS DETAIL DOES NOT SHOW A WATERSTOP;
 WATERPROOFING IS NOT CONTINUOUS TO PROTECT THE FOOTING
 FBC 1805.3.3.
  
 SEE ALSO COMMENTS FROM VIBROFLOTATION PERMIT
 APPLICATION 15031039 (IT IS NOT CLEAR AT THIS POINT
 WHETHER THIS WILL BE A SEPARATE PERMIT OR INCORPORATED
 INTO THIS FOUNDATION PERMIT):
  
 15. FBC 3304.1, IT IS RECOMMENDED THAT CONTRACTOR
 ADVISE THE RESIDENTS ADJACENT TO PROPOSED CONSTRUCTION
 OF WORK PRIOR TO COMMENCEMENT. PROPERTY OWNERS IN THE
 ADJACENT TOWNHOUSES HAVE EXPRESSED CONCERN REGARDING
 THE STRUCTURAL IMPACT OF CONSTRUCTION AND CONTRACTOR
 HAS EXPLAINED HOW THIS WILL BE ADDRESSED, FBC 3307.1.
 PER CONTRACTOR, A STRUCTURAL ANALYSIS OF THE ADJACENT
 STRUCTURES WILL BE PERFORMED AND DOCUMENTED PRIOR TO
 CONSTRUCTION.
  
 IF THE ANALYSIS DISCUSSED IS NOT DONE PRIOR TO ISSUANCE
 OF THIS VIBROFLOTATION PERMIT, CONTRACTOR IS TO PROVIDE
 A LETTER STATING WHY THIS IS NOT NECESSARY AT THIS
 TIME. IT IS RECOMMENDED THAT CONTRACTOR PROVIDE
 INFORMATION REGARDING THE TIMING AND NATURE OF THIS
 PERMIT TO THE RESIDENTS PRIOR TO COMMENCEMENT.
  
 16. ADVISORY ONLY - CONSTRUCTION HOURS ARE 7AM - 7PM
 MONDAY THROUGH FRIDAY; 8AM - 8PM WEEKENDS, CITY OF WEST
 PALM BEACH MUNICIPAL CODE SECTION 34-72. A WRITTEN
 EXCEPTION MAY BE GRANTED BY THE BUILDING OFFICIAL;
 PLEASE SUBMIT ANY SUCH REQUESTS (IF NEEDED) TIMELY TO
 [email protected], CC [email protected] AND [email protected].
  
 17. FOR ALL NEW SHEETS FOR THIS PERMIT AND ALL NEW
 SHEETS SUBMITTED ON OTHER RELATED PERMITS:
  
 A. INCLUDE THE ARCHITECT BUSINESS NUMBER ON EACH SHEET,
 FS481.
 B. CHANGE ADDRESS FROM "650 OKEECHOBEE BL" TO "1099
 FLORIDA AVE."
  
  
  
  
  
  