2015-02-12 09:51:06 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. INFORMATIONAL ONLY - A COPY OF THE THRESHOLD |
| INSPECTION PLAN PREPARED BY THOMAS J. ROGERS, PE, |
| ONM&J, HAS BEEN ROUTED TO KEN CONRAD, CHIEF BUILDING |
| INSPECTOR. |
| |
| 2. INFORMATIONAL ONLY - AS THIS IS A THRESHOLD JOB, |
| THREE SETS OF ALL DOCUMENTS REQUIRED. |
| |
| 3. INFORMATIONAL ONLY - IMPORTANT NOTICE: EFFECTIVE |
| MARCH 2, 2015 |
| |
| ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| ELECTRONICALLY |
| |
| UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| SUBMISSION OPTIONS ARE AS FOLLOWS: |
| |
| 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 2 INCLUDE ON A CD WITH DESIGN PROFESSIONAL DIGITAL |
| SIGNATURES AS APPLICABLE; USE THE REQUIRED NAMING |
| CONVENTION FOR EACH DOCUMENT |
| 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| |
| ADDITIONAL INFORMATION AND SPECIFIC PROCEDURES WILL BE |
| SENT TO YOU WHEN AVAILABLE |
| |
| FOR THIS THRESHOLD JOB, CONTRACTOR IS RESPONSIBLE FOR |
| PROVIDING A SET OF ALL DOCUMENTS TO THE SPECIAL |
| INSPECTOR. |
| |
| 4. FS 553.79(5), FBC 2010 110.3.7.1, THE ENFORCING |
| AGENCY SHALL REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| ENGINEER OR ARCHITECT OF RECORD. PROVIDE A SPECIAL |
| INSPECTOR AGREEMENT SIGNED BY ALL PARTIES. |
| |
| PROVIDE A RESUME OF INSPECTION EXPERIENCE AND COPIES OF |
| ALL CERTIFICATES/LICENSES AS APPLICABLE FOR PROPOSED |
| INSPECTORS. |
| |
| PLEASE FEEL FREE TO CONTACT ME OR KEN CONRAD, CHIEF |
| BUILDING INSPECTOR, FOR MORE INFORMATION |
| ([email protected], 561-805-6666). |
| |
| 5. PROVIDE THE GEOTECHNICAL REPORT REFERRED TO ON SHEET |
| S7.1 (TIERRA SOUTH 7/15/14), FBC 2010 BUILDING 1803.5. |
| |
| 6. DOCUMENTS PREPARED BY AN ARCHITECT AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS |
| FS481. THE ARCHITECTURAL SHEETS ARE MARKED *FOR |
| REFERENCE ONLY*. THE PAGES PROVIDED ARE REQUIRED |
| INFORMATION TO OBTAIN A FOUNDATION PERMIT, FBC 107. |
| |
| 6. THRESHOLD BLDG, REQUIRED STATEMENT: |
| |
| W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S |
| KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| PLEASE INCLUDE THE THRESHOLD DESIGN COMPLIANCE |
| STATEMENT ON THE ARCHITECTURAL SHEETS (ALREADY ON THE |
| ENGINEERING SHEETS). |
| |
| 7. PLEASE INCORPORATE THE FOLLOWING ADVISORY NOTICE |
| INTO THE PLAN: |
| |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 110.7 IMPACT OF CONSTRUCTION. ALL CONSTRUCTION ACTIVITY |
| REGULATED BY THIS CODE SHALL BE PERFORMED IN A MANNER |
| SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF ADJACENT |
| PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT |
| SAID PROPERTY PURSUANT TO A CONSENT GRANTED BY THE |
| APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS |
| AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST, |
| NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE |
| STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC |
| SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON |
| EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE |
| OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE |
| DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A |
| PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE |
| SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| OF THE FINAL INSPECTION. |
| |
| 8. ALTHOUGH LOCATION OF PROPOSED GARAGE RELATIVE TO LOT |
| LINES AND EXISTING STRUCTURE APPEAR COMPLIANT, IT IS |
| NOT POSSIBLE TO DETERMINE CODE COMPLIANCE WITHOUT THE |
| INFORMATION REQUESTED BELOW. PLEASE REVISE PLAN TO |
| INCLUDE THE FOLLOWING INFORMATION IN ORDER TO |
| DEMONSTRATE COMPLIANCE WITH FBC 705.8: |
| |
| SHOW LOCATION OF ASSUMED PROPERTY LINE (BETWEEN THE |
| EXISTING CONVENTION CENTER AND PROPOSED PARKING |
| GARAGE); PLEASE REVISE PLAN TO SHOW DISTANCE OF EACH |
| BUILDING TO THE ASSUMED PROPERTY LINE (FBC 705.3) |
| |
| BUILDING CONSTRUCTION TYPE (FBC 602) AND OCCUPANCY |
| CLASSIFICATION OF EXISTING CONVENTION CENTER AND |
| PROPOSED PARKING GARAGE |
| |
| SPRINKLER INFORMATION FOR EXISTING CONVENTION CENTER |
| AND PROPOSED PARKING GARAGE (FBC TABLE 503) |
| |
| 9. SCOPE UNDER THIS FOUNDATION PERMIT PER CONTRACTOR |
| INCLUDES VIBROFLOTATION, EXCAVATION OF LOWER LEVEL, |
| CONCRETE WORK FOR FOOTINGS, ELEVATOR PITS, FOUNDATION |
| WALL AND FIRST LIFT OF COLUMNS. A TRENCH DRAIN IS SHOWN |
| ON S1B WITH A REFERENCE TO ARCHITECTURAL SHEETS, IS |
| THIS ALSO IN THE SCOPE OF THIS PERMIT? IF INCLUDED, |
| PROVIDE A DETAIL, FBC 107. IF NOT INCLUDED, DISREGARD |
| COMMENT. |
| |
| 10. PLEASE PROVIDE COMPLIANCE IN CREATING A SECURE SITE |
| AND IN COMPLIANCE WITH 3306.1 PROTECTION OF PEDESTRIANS |
| AND 3306.5 AND 3306.6 BARRIERS. |
| |
| 11. SHEET S7.1, SEVERAL REFERENCE STANDARDS REFER TO |
| *LATEST EDITION*. SEE FBC CHAPTER 35 AND REVISE TO |
| INDICATE THE STANDARD VERSION USED FOR DESIGN. IF A |
| STANDARD USED IN THE DESIGN OF THIS STRUCTURE IS NOT |
| THE STANDARD SPECIFIED BY FBC CHAPTER 35, THIS SHOULD |
| BE SUBMITTED USING FBC 104.11, ALTERNATIVE MATERIALS |
| AND METHODS. PLEASE CONTACT ME IF YOU NEED FURTHER |
| ASSISTANCE. |
| |
| |
| |
| |