2015-02-10 11:46:17 | PLAN REVIEW COMMENTS |
| |
| 2ND REVIEW: FBC 2010 |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY ELECTRICAL |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE 3/4" CONDUIT SHOWN ON THE REVISED ELECTRICAL |
| RISER DIAGRAM BETWEEN THE EXISTING 200 AMP PANEL AND |
| THE NEW 150 AMP SUB-PANEL IS TOO SMALL FOR THE 150 AMP |
| SUB-PANEL. NEC 310.15 |
| |
| 2) SPECIFY THE WIRE SIZES AND NUMBER OF FEEDERS AND |
| CONDUIT TYPE AND SIZE FOR THE 150 AMP PANEL. NEC 310.15 |
| |
| 3) SPECIFY THE TYPE OF CONDUIT THAT IS INSTALLED (IE. |
| RIGID METAL CONDUIT (RMC), RIGID PVC, EMT, ETC.) FBC |
| 107.2.1 NOTE IF PVC CONDUIT IS AN EQUIPMENT GROUNDING |
| CONDUCTOR IS REQUIRED. NEC 250.118 |
| |
| 4) PROVIDE A PANEL SCHEDULE AND LOAD CALCULATIONS FOR |
| BOTH PANELS ON THE REVISED ELECTRICAL PLANS. NEC 220.40 |
| & FBC 107.3.5.3 |
| |
| 5) SHOW THAT THE FEEDERS FOM THE 200AMP PANEL TO THE |
| 150 AMP SUB-PANEL HAVE OVERCURRENT PROTECTION. NEC |
| 240.4 |
| |
| 6) THE INTERSYSTEM BONDING IS NOT DRAWN CORRECTLY. THE |
| DIAGRAM APPEARS TO SHOW #6 MIN EQUIPMENT GROUNDS FROM |
| THE MAIN DISCONNECT, 200 AMP PANEL AND 150 AMP |
| SUB-PANEL TIED TO THE INTERSYSTEM BONDING. THE |
| EQUIPMENT GROUND WIRE IS REQUIRED IF PVC CONDUIT IS |
| USED, IT IS NOT REQUIRED FOR METAL CONDUIT. THE |
| INTERSYSTEM BONDING IS REQUIRED FOR BONDING "LIMITED |
| ENERGY" SYSTEMS SUCH AS COMMUNICATIONS, RADIO, |
| TELEPHONE, TV AND CATV CIRCUITS TOGETHER TO THE SERVICE |
| GROUNDING AND BONDING SYSTEM. NEC 250.94 |
| |
| 7) THERE SHOULD NOT BE A #6 EQUIPMENT GROUND WIRE |
| BETWEEN THE METER CAN AND THE MAIN DISCONNECT. NEC |
| 250.110 |
| |
| 8) THE ADDRESS SHOULD BE 2015 BRADLEY CT. AND NOT 2015 |
| BRADLEY CY. FBC 107.2.1 |
| |
| 9) THE REVISED ELECTRICAL RISER DIAGRAM SPECIFIES A #2 |
| CU GROUNDING ELECTRODE CONDUCTOR. PLEASE VERIFY THAT |
| THIS IS ACCURATE. FBC 107.2.1 |