Plan Review Notes
Plan Review Notes For Permit 15010622
Permit Number 15010622
Review Stop E
Sequence Number 1
Notes
Date Text
2015-01-26 07:30:38PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE APPROVED
 ELECTRICAL PLANS WERE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER, DANIEL J. MOSS. ANY REVISIONS TO THE
 DRAWINGS ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ENGINEER. FLORIDA STATUTES 471
  
 2) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 3) NEC 230.70 - MEANS SHALL BE PROVIDED TO DISCONNECT
 ALL CONDUCTORS IN A BUILDING OR OTHER STRUCTURE FROM
 THE SERVICE ENTRANCE CONDUCTORS.
  
 4) FBC 107.1.2 PLEASE CLARIFY THE SIZE OF THE
 CONDUCTORS AT THE WEATHER HEAD. THE DRAWING HAS 3-1#1
 C.U. DID YOU MEAN 3-#1/0 CU OR 3-#1 CU ?
  
  