Plan Review Notes For Permit 15010622 |
Permit Number |
15010622 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-26 07:30:38 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. THE APPROVED | | ELECTRICAL PLANS WERE SIGNED AND SEALED BY A FLORIDA | | LICENSED ENGINEER, DANIEL J. MOSS. ANY REVISIONS TO THE | | DRAWINGS ARE REQUIRED TO BE SIGNED AND SEALED BY THE | | ENGINEER. FLORIDA STATUTES 471 | | | | 2) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL | | BE PROVIDED. | | | | 3) NEC 230.70 - MEANS SHALL BE PROVIDED TO DISCONNECT | | ALL CONDUCTORS IN A BUILDING OR OTHER STRUCTURE FROM | | THE SERVICE ENTRANCE CONDUCTORS. | | | | 4) FBC 107.1.2 PLEASE CLARIFY THE SIZE OF THE | | CONDUCTORS AT THE WEATHER HEAD. THE DRAWING HAS 3-1#1 | | C.U. DID YOU MEAN 3-#1/0 CU OR 3-#1 CU ? | | | | |
|