2015-01-24 03:39:041) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS
 FOR THE PUMP TO BE USED IN THE SUMP. WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 2) IF THE SUMP BASIN IS A PRE-MANUFACTURED UNIT, SUBMIT
 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR THE
 SUMP BASIN.WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) THE SUMP PIT/BASIN SHALL BE NOT LESS THAN 18 INCHES
 IN DIAMETER AND 24 INCHES DEEP AND FITTED WITH A
 GAS-TIGHT REMOVABLE COVER. 2010 FPC SEC.712.3.2.
 4) THE SUMP DISCHARGE LINE SHALL CONNECT TO THE
 BUILDING SEWER OR TO A WYE FITTING IN THE BUILDING
 DRAIN AND A MINIMUM 10 FEET FROM A STACK PER 2010 FPC
 712.3.5.
 5) SUBMIT 2 COPIES OF THE MANUF. SPECS/INSTALLATION
 MANUAL FOR THE TANKLESS WATER HEATER.WPB AMEND. TO 2010
 FBC SEC.107.2.1.
  