Plan Review Notes For Permit 15010590 |
Permit Number |
15010590 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-24 03:39:04 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS | | FOR THE PUMP TO BE USED IN THE SUMP. WPB AMEND. TO 2010 | | FBC SEC.107.2.1. | | 2) IF THE SUMP BASIN IS A PRE-MANUFACTURED UNIT, SUBMIT | | 2 COPIES OF THE MANUFACTURER'S SPECIFICATIONS FOR THE | | SUMP BASIN.WPB AMEND. TO 2010 FBC SEC.107.2.1. | | 3) THE SUMP PIT/BASIN SHALL BE NOT LESS THAN 18 INCHES | | IN DIAMETER AND 24 INCHES DEEP AND FITTED WITH A | | GAS-TIGHT REMOVABLE COVER. 2010 FPC SEC.712.3.2. | | 4) THE SUMP DISCHARGE LINE SHALL CONNECT TO THE | | BUILDING SEWER OR TO A WYE FITTING IN THE BUILDING | | DRAIN AND A MINIMUM 10 FEET FROM A STACK PER 2010 FPC | | 712.3.5. | | 5) SUBMIT 2 COPIES OF THE MANUF. SPECS/INSTALLATION | | MANUAL FOR THE TANKLESS WATER HEATER.WPB AMEND. TO 2010 | | FBC SEC.107.2.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|