2015-01-22 15:20:56 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- EAGLE ROOF TILE FLORIDA PRODUCT APPROVAL FL7473-R3 |
| SUBMITTED DOESN'T SPECIFY THE ATTACHMENT RESISTANCE |
| VALUE WITH THE USE OF 3M COMPONENT FOAM ROOF TILE |
| ADHESIVE AH-160. SEE LIMITATION 5.5 ON PAGE 3 OF 4 OF |
| FL7473-R3. ON THE OTHER HAND, ROOF TILE ADHESIVE AH-160 |
| NOA 14-0805.01 SUBMITTED REQUIRES THE ROOF TILE |
| ASSEMBLY TO LIST THE AH-160 AND THE CORRESPONDING |
| ATTACHMENT RESISTANCE VALUE. PLEASE PROVIDE PROPER |
| PRODUCT APPROVALS FOR ROOF TILE AND ROOF TILE ADHESIVE |
| SHOWING THE ATTACHMENT RESISTANCE. DCA RULE 9N-3. |
| |
| 2- POLYSTICK TU PLUS UNDERLAYMENT FLORIDA PRODUCT |
| APPROVAL FL5259-R20 SUBMITTED. CLEARLY IDENTIFY WHICH |
| ASSEMBLY IS GOING TO BE INSTALLED. DIRECT BOND DECK OR |
| BOND TO MECHANICALLY ATTACHED BASE LAYER: |
| A) IF USING THE DIRECT BOND TO DECK, THEN KEEP IN MIND |
| THAT SEC. 5.5.4.1 ON PAGE 5 OF 11 OF FL5259-R20 SHOWS A |
| MAXIMUM DESIGN PRESSURES OF -90 PSF . IT DOESN'T MEET |
| THE DESIGN PRESSURES AT CORNER AREAS. THEREFORE, IT |
| CAN'T BE USED FOR CORNER AREAS. NEED TO USE ANOTHER |
| ASSEMBLY WITH HIGHER DESIGN PRESSURES FOR CORNER AREAS. |
| |
| B) IF USING THE BOND TO MECHANICALLY ATTACHED BASE |
| LAYER, THEN PROVIDE THE SPECIFICATIONS FOR THE BASE |
| SHEET FASTENING SHOWING COMPLIANCE WITH THE DESIGN |
| PRESSURES OF SEC. R301.1 OF 2010 FBC-RESIDENTIAL. SEE |
| SEC. 5.5.3 ON PAGE 5 OF 11 OF FL5259-R20. |
| |
| 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION WAS UPDATED TO $24,157, SEC. 109.3 CITY |
| AMENDMENTS TO FBC. THE PERMIT FEE BALANCE IS $566.94. |
| |