2015-01-22 15:20:56RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- EAGLE ROOF TILE FLORIDA PRODUCT APPROVAL FL7473-R3
 SUBMITTED DOESN'T SPECIFY THE ATTACHMENT RESISTANCE
 VALUE WITH THE USE OF 3M COMPONENT FOAM ROOF TILE
 ADHESIVE AH-160. SEE LIMITATION 5.5 ON PAGE 3 OF 4 OF
 FL7473-R3. ON THE OTHER HAND, ROOF TILE ADHESIVE AH-160
 NOA 14-0805.01 SUBMITTED REQUIRES THE ROOF TILE
 ASSEMBLY TO LIST THE AH-160 AND THE CORRESPONDING
 ATTACHMENT RESISTANCE VALUE. PLEASE PROVIDE PROPER
 PRODUCT APPROVALS FOR ROOF TILE AND ROOF TILE ADHESIVE
 SHOWING THE ATTACHMENT RESISTANCE. DCA RULE 9N-3.
  
 2- POLYSTICK TU PLUS UNDERLAYMENT FLORIDA PRODUCT
 APPROVAL FL5259-R20 SUBMITTED. CLEARLY IDENTIFY WHICH
 ASSEMBLY IS GOING TO BE INSTALLED. DIRECT BOND DECK OR
 BOND TO MECHANICALLY ATTACHED BASE LAYER:
 A) IF USING THE DIRECT BOND TO DECK, THEN KEEP IN MIND
 THAT SEC. 5.5.4.1 ON PAGE 5 OF 11 OF FL5259-R20 SHOWS A
 MAXIMUM DESIGN PRESSURES OF -90 PSF . IT DOESN'T MEET
 THE DESIGN PRESSURES AT CORNER AREAS. THEREFORE, IT
 CAN'T BE USED FOR CORNER AREAS. NEED TO USE ANOTHER
 ASSEMBLY WITH HIGHER DESIGN PRESSURES FOR CORNER AREAS.
  
 B) IF USING THE BOND TO MECHANICALLY ATTACHED BASE
 LAYER, THEN PROVIDE THE SPECIFICATIONS FOR THE BASE
 SHEET FASTENING SHOWING COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 OF 2010 FBC-RESIDENTIAL. SEE
 SEC. 5.5.3 ON PAGE 5 OF 11 OF FL5259-R20.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO $24,157, SEC. 109.3 CITY
 AMENDMENTS TO FBC. THE PERMIT FEE BALANCE IS $566.94.
  