2015-03-30 16:58:19 | ****CORRECTIONS**** |
| EDITED ON 3/31/2015 |
| |
| CONTRACTOR PROVIDED A HARD COPY OF THE "BUILDING UNDER |
| CONSTRUCTION" ELEVATION CERTIFICATE PREVIOUSLY SENT VIA |
| EMAIL |
| ISSUE WAS DISCUSSED AT LENGTH ON THE TELEPHONE WITH |
| CONTRACTOR |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| CORRECTIONS FOR ELEVATION CERTIFICATE (JOB #14-08-011) |
| DATED 1/29/2015 PREPARED BY ERNEST W. DUNCAN, BASELINE |
| ENGINEERING & LAND SURVEYING, "BUILDING UNDER |
| CONSTRUCTION": |
| |
| 1. A1, OWNER IS SHOWN AS "KELLY RESIDENCE" BUT THE |
| OWNERS OF RECORD ARE DONALD FROUDE AND KIMBERLY FROUDE. |
| PLEASE CORRELATE. |
| |
| 2. A5, LAT/LONG TO BE PROVIDED TO 1 DECIMAL PLACE OR |
| BETTER WHEN USING DEGRESS, MINUTES SECONDS FORMAT. ALSO |
| PLEASE CONFIRM THE COORDINATES; THIS TO BE THE CENTER |
| FRONT OF THE BUILDING AND ACCURATE WITHIN 66 FEET. THE |
| COORDINATES APPEAR TO BE LOCATED IN THE ADJACENT PARCEL |
| (OVER 66' AWAY). |
| |
| 3. ADVISORY ONLY; COLOR PHOTOGRAPHS WILL BE REQUIRED |
| FOR THE "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE. |
| PHOTOGRAPHS OF THE INSTALLED FLOOD VENTS, IF INSTALLED, |
| WILL ALSO BE REQUIRED. IF ENGINEERED FLOOD VENTS ARE |
| INSTALLED, THE ENGINEERING OR PRODUCT APPROVAL IS TO BE |
| INCLUDED WITH THE ELEVATION CERTIFICATE. |
| |
| 4. ITEM A9; SEE SHEETS A2.0 (DEMO PLAN) AND A3.0, ROOM |
| 105 IS SHOWN AS A "GREAT ROOM" BUT APPEARS TO BE A |
| GARAGE (SEE A5.0, NORTH ELEVATION). ELEVATION |
| CERTIFICATE SHOWS GARAGE AS 400 SF, PAPA RECORDS SHOW |
| THE GARAGE AS 440 SF. PLEASE RECONCILE THE |
| DISCREPANCIES. |
| |
| 5. A9, NO FLOOD VENTS INDICATED, BUT ITEM C2D SHOWS THE |
| GARAGE AT 7.0 FEET. SEE CITY OF WEST PALM BEACH |
| MUNICIPAL CODE 94-546(B), A 6INCH FREEBOARD REQUIRED |
| FOR ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS. |
| THIS CAN BE VIEWED AT WWW.MUNICODE.COM. |
| |
| SEE FBC 2010 EXISTING BUILDING 601.3: FLOOD HAZARD |
| AREAS. IN FLOOD HAZARD AREAS, ALTERATIONS THAT |
| CONSTITUTE SUBSTANTIAL IMPROVEMENT SHALL REQUIRE THAT |
| THE BUILDING COMPLY WITH SECTION 1612 OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| FBC 2010 EXISTING BUILDING 1003.5 FOR ADDITIONAL |
| REQUIREMENTS. |
| |
| SEE FBC 1612, SUBSTANTIAL IMPROVEMENT. |
| |
| OPTIONS FOR GARAGE ARE TO RAISE TO 7.5' OR TO INSTALL |
| FLOOD VENTS WHICH WILL ALLOW THE WATER TO ENTER AND |
| EXIT. |
| |
| ISO HAS PROVIDED INITIAL CLARIFICATION ON THIS ISSUE. |
| PLEASE BE ADVISED THAT THE BUILDING OFFICIAL HAS |
| REQUESTED FURTHER CLARIFICATION ON 3/30/15 WHICH MAY |
| AFFECT YOUR PROJECT. THIS COMMENT LIST WILL BE REVISED |
| BASED ON ISO'S CONVERSATION WITH THE BUILDING OFFICIAL |
| IF NEW INFORMATION OR GUIDANCE AFFECTS YOUR PROJECT. |
| |
| 6. C2B IS NA FOR NEXT HIGHER FLOOR; PERMIT DOCUMENTS |
| (SEE SHEET A4.0) SHOW AN "EXISTING SECOND FLOOR." |
| |
| 7. C2E SHOWS THE LOWEST MACHINERY/EQUIPMENT AS 6.80; |
| THIS IS ALSO REQUIRED TO BE A MINIMUM OF 7.5'. |
| |
| 8. SECTION D, LATITUDE / LONGITUDE PROVIDED BY A |
| SURVEYOR, THE "NO" BOX IS CHECKED. AS FLORIDA STATUTE |
| ONLY ALLOWS SURVEYORS TO PREPARE ELEVATION CERTIFICATES |
| (AND NOT ARCHITECTS / ENGINEERS AS PERMITTED IN OTHER |
| STATES), THIS BOX SHOULD ALWAYS BE "YES". IT IS |
| UNDERSTOOD THAT THE SURVEYOR RELIES ON OTHER ENTITIES |
| FOR THIS DATA - TYPICAL SOURCES ARE GOOGLE EARTH (WHICH |
| SURVEYOR USED FOR THIS ELEVATION CERTIFICATE), |
| LABINS.ORG, PALM BEACH COUNTY GIS, ETC. |
| |
| 9. SECTION D, DESCRIBE EQUIPMENT FROM C2E. |
| |
| 10. SECTION D, COMMENT STATES THAT THIS "BUILDING IS A |
| CABANA." IT IS NOT CLEAR WHICH STRUCTURE THIS ELEVATION |
| CERTIFICATE REPRESENTS; PLEASE PROVIDE CLARIFICATION. |
| CABANA APPEARS TOO SMALL TO HAVE A GARAGE. AN ELEVATION |
| CERTIFICATE IS REQUIRED FOR THE HOUSE. IF THIS |
| ELEVATION CERTIFICATE IS FOR BOTH STRUCTURES, PROVIDE |
| CLARIFICATION IN THE DESCRIPTION AND THE COMMENTS. |
| |
| |
| |
| |
| |
| |