2015-03-30 16:58:19****CORRECTIONS****
 EDITED ON 3/31/2015
  
 CONTRACTOR PROVIDED A HARD COPY OF THE "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE PREVIOUSLY SENT VIA
 EMAIL
 ISSUE WAS DISCUSSED AT LENGTH ON THE TELEPHONE WITH
 CONTRACTOR
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CORRECTIONS FOR ELEVATION CERTIFICATE (JOB #14-08-011)
 DATED 1/29/2015 PREPARED BY ERNEST W. DUNCAN, BASELINE
 ENGINEERING & LAND SURVEYING, "BUILDING UNDER
 CONSTRUCTION":
  
 1. A1, OWNER IS SHOWN AS "KELLY RESIDENCE" BUT THE
 OWNERS OF RECORD ARE DONALD FROUDE AND KIMBERLY FROUDE.
 PLEASE CORRELATE.
  
 2. A5, LAT/LONG TO BE PROVIDED TO 1 DECIMAL PLACE OR
 BETTER WHEN USING DEGRESS, MINUTES SECONDS FORMAT. ALSO
 PLEASE CONFIRM THE COORDINATES; THIS TO BE THE CENTER
 FRONT OF THE BUILDING AND ACCURATE WITHIN 66 FEET. THE
 COORDINATES APPEAR TO BE LOCATED IN THE ADJACENT PARCEL
 (OVER 66' AWAY).
  
 3. ADVISORY ONLY; COLOR PHOTOGRAPHS WILL BE REQUIRED
 FOR THE "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE.
 PHOTOGRAPHS OF THE INSTALLED FLOOD VENTS, IF INSTALLED,
 WILL ALSO BE REQUIRED. IF ENGINEERED FLOOD VENTS ARE
 INSTALLED, THE ENGINEERING OR PRODUCT APPROVAL IS TO BE
 INCLUDED WITH THE ELEVATION CERTIFICATE.
  
 4. ITEM A9; SEE SHEETS A2.0 (DEMO PLAN) AND A3.0, ROOM
 105 IS SHOWN AS A "GREAT ROOM" BUT APPEARS TO BE A
 GARAGE (SEE A5.0, NORTH ELEVATION). ELEVATION
 CERTIFICATE SHOWS GARAGE AS 400 SF, PAPA RECORDS SHOW
 THE GARAGE AS 440 SF. PLEASE RECONCILE THE
 DISCREPANCIES.
  
 5. A9, NO FLOOD VENTS INDICATED, BUT ITEM C2D SHOWS THE
 GARAGE AT 7.0 FEET. SEE CITY OF WEST PALM BEACH
 MUNICIPAL CODE 94-546(B), A 6INCH FREEBOARD REQUIRED
 FOR ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS.
 THIS CAN BE VIEWED AT WWW.MUNICODE.COM.
  
 SEE FBC 2010 EXISTING BUILDING 601.3: FLOOD HAZARD
 AREAS. IN FLOOD HAZARD AREAS, ALTERATIONS THAT
 CONSTITUTE SUBSTANTIAL IMPROVEMENT SHALL REQUIRE THAT
 THE BUILDING COMPLY WITH SECTION 1612 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 FBC 2010 EXISTING BUILDING 1003.5 FOR ADDITIONAL
 REQUIREMENTS.
  
 SEE FBC 1612, SUBSTANTIAL IMPROVEMENT.
  
 OPTIONS FOR GARAGE ARE TO RAISE TO 7.5' OR TO INSTALL
 FLOOD VENTS WHICH WILL ALLOW THE WATER TO ENTER AND
 EXIT.
  
 ISO HAS PROVIDED INITIAL CLARIFICATION ON THIS ISSUE.
 PLEASE BE ADVISED THAT THE BUILDING OFFICIAL HAS
 REQUESTED FURTHER CLARIFICATION ON 3/30/15 WHICH MAY
 AFFECT YOUR PROJECT. THIS COMMENT LIST WILL BE REVISED
 BASED ON ISO'S CONVERSATION WITH THE BUILDING OFFICIAL
 IF NEW INFORMATION OR GUIDANCE AFFECTS YOUR PROJECT.
  
 6. C2B IS NA FOR NEXT HIGHER FLOOR; PERMIT DOCUMENTS
 (SEE SHEET A4.0) SHOW AN "EXISTING SECOND FLOOR."
  
 7. C2E SHOWS THE LOWEST MACHINERY/EQUIPMENT AS 6.80;
 THIS IS ALSO REQUIRED TO BE A MINIMUM OF 7.5'.
  
 8. SECTION D, LATITUDE / LONGITUDE PROVIDED BY A
 SURVEYOR, THE "NO" BOX IS CHECKED. AS FLORIDA STATUTE
 ONLY ALLOWS SURVEYORS TO PREPARE ELEVATION CERTIFICATES
 (AND NOT ARCHITECTS / ENGINEERS AS PERMITTED IN OTHER
 STATES), THIS BOX SHOULD ALWAYS BE "YES". IT IS
 UNDERSTOOD THAT THE SURVEYOR RELIES ON OTHER ENTITIES
 FOR THIS DATA - TYPICAL SOURCES ARE GOOGLE EARTH (WHICH
 SURVEYOR USED FOR THIS ELEVATION CERTIFICATE),
 LABINS.ORG, PALM BEACH COUNTY GIS, ETC.
  
 9. SECTION D, DESCRIBE EQUIPMENT FROM C2E.
  
 10. SECTION D, COMMENT STATES THAT THIS "BUILDING IS A
 CABANA." IT IS NOT CLEAR WHICH STRUCTURE THIS ELEVATION
 CERTIFICATE REPRESENTS; PLEASE PROVIDE CLARIFICATION.
 CABANA APPEARS TOO SMALL TO HAVE A GARAGE. AN ELEVATION
 CERTIFICATE IS REQUIRED FOR THE HOUSE. IF THIS
 ELEVATION CERTIFICATE IS FOR BOTH STRUCTURES, PROVIDE
 CLARIFICATION IN THE DESCRIPTION AND THE COMMENTS.
  
  
  
  
  
  