Plan Review Notes For Permit 15010463 |
Permit Number |
15010463 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-29 11:30:15 | 1. FBC 107.3.5.3. PROVIDE PANEL SCHEDULE AND CIRCUITRY | | FOR OUTLETS ON PLANS. | | 2. N.E.C. 210.11(C)1. IDENTIFY A MININUM OF TWO SMALL | | APPLIANCE CIRCUITS SUPPLYING KITCHEN COUNTERTOP | | RECEPTACLES. | | 3. FBC SECTION R314 LOCATION OF SMOKE ALARMS | | 4. N.E.C. 210.12 ARC FAULT PROTECTION FOR OUTLETS ON 15 | | AND 20 AMPERE BRANCH CIRCUITS FOR AREAS SPECIFIED IN | | THIS CODE SECTION,(T.V. ENTERTAINMENT AREA.) | | 5. N.E.C. 406.11 TAMPER RESISTANT RECEPTACLES. |
|