2015-01-20 09:05:45 | 1) INDICATE ON THE PLANS THE TYPE OF PIPING TO BE |
| INSTALLED ( UNDERGROUND & ABOVEGROUND) FOR THE POOL |
| HEATER AND THE GENERATOR. WPB AMEND. TO FBC SEC. |
| 107.2.1. |
| 2) SUBMIT DETAILS AS TO HOW THE APPLIANCES WILL BE |
| ANCHORED TO COMPLY WITH THE WINDLOAD REQUIREMENTS FOR |
| THIS WIND ZONE. 2010 FBC, RESIDENTIAL CODE SEC.G2404.6. |
| 3) INDICATE IF THE STRUCTURE IS LOCATED IN FLOOD HAZARD |
| AREA. IF APPLICABLE, THE GAS EQUIPMENT SHALL BE LOCATED |
| AT OR ABOVE THE DESIGN FLOOD ELEVATION PER THE 2010 |
| FBCR SEC. G2404.7 & R322. |
| 4) INDICATE THE BTU LOAD OF EACH APPLIANCE ON THE |
| DRAWING AND THE TOTAL BTU LOAD ON THE SYSTEM. 2010 FBCR |
| SEC.G2413.2. |
| 5) INDICATE ON THE PLANS THE LONGEST DEVELOPED LENGTH |
| OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET.2010 FBCR SEC. G2413..4.1. |
| 6) SUBMIT A SITE PLAN/SURVEY THAT SHOWS THE HOUSE AND |
| PROPERTY LINES AND THE LOCATION OF THE GENERATOR AND |
| POOL HEATER IN RELATION TO THE STRUCTURE.THE GENERATOR |
| SHALL BE A MINIMUM OF 5 FEET FROM THE EXTERIOR WALL OF |
| THE STRUCTURE PER NFPA 37 SEC.4.1.4. |
| 7) SUBMIT A SITE PLAN/SURVEY THAT SHOWS THE DISTANCE OF |
| THE POOL HEATER AND GENERATOR FROM THE PROPERTY |
| LINES.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 8) INDICATE THE DELIVERY PRESSURE ( PSI) OF THE GAS ON |
| THE PLANS.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 9) SUBMIT 2 COPIES OF THE APPLICABLE SIZING TABLE FROM |
| CHAPTER 24 OF THE 2010 FBCR FOR EACH TYPE OF PIPE |
| MATERIAL BEING INSTALLED.2010 FBCR SEC.G2413.3. |
| 10) SHOW THE LOCATION OF ANY MEDIUM PRESSURE |
| REGULATORS. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 11) INDICATE THE TYPE OF GAS ( LP OR NATURAL).WPB |
| AMEND.TO 2010 FBC SEC.107.2.1. |
| |