2015-02-05 08:06:11PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBCR-M1602.2 OUTDOOR AND RETURN AIR FOR A FORCED-AIR
 HEATING OR COOLING SYSTEM SHALL NOT BE TAKEN FROM THE
 FOLLOWING LOCATIONS: 4. A CLOSET, BATHROOM, TOILET
 ROOM, KITCHEN, GARAGE, MECHANICAL ROOM, BOILER ROOM,
 FURNACE ROOM, UNCONDITIONED ATTIC OR OTHER DWELLING
 UNIT. RETURN CAN NOT BE IN THE KITCHEN WALL.
  
 2) FBCR- M1602.4 RESTRICTED RETURN AIR OCCURS IN
 BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL ZONES AND
 CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE RETURN
 GRILL OR WHEN CEILING SPACES ARE USED AS RETURN PLENUMS
 AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE PORTION
 OF THE RETURN PLENUM TO ANOTHER. PROVISIONS SHALL BE
 MADE IN BOTH RESIDENTIAL AND COMMERCIAL BUILDINGS TO
 AVOID UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS
 CAUSED BY RESTRICTED RETURN AIR. EXCEPTIONS:
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
 THE TRANSFER GRILLES ARE TOO SMALL IN THE MASTER
 BEDROOM (250 CFM = 125 SQIN OF GRILL AREA) , BEDROOM 2
 (140 CFM = 70 SQIN OF GRILL AREA) AND BEDROOM 4 (125
 CFM = 62.5 SQIN OF GRILL AREA).
  
 4) THERE IS WHAT APPEARS TO BE A RETURN WITH 20 CFM
 SHOWN IN THE HALLWAY IN FRONT OF THE LINEN CLOSEST.
 PLEASE CLARIFY. FBC 107.2.1