Plan Review Notes
Plan Review Notes For Permit 15010449
Permit Number 15010449
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-05 10:35:01PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL SERVICE EQUIPMENT ON THE PLANS.
  
 2) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 3) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 4) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 5) NEC 210.52 (B) IN THE KITCHEN, PANTRY, BREAKFAST
 ROOM, DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT,
 THE TWO OR MORE 20 - AMPERE BRANCH CIRCUITS REQUIRED BY
 210.11 (C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS
 FOR REFRIGERATION EQUIPMENT. SEE EXCEPTIONS FOR
 SWITCHED RECEPTACLES AND REFRIGERATION SUPPLIED BY AN
 INDIVIDUAL BRANCH CIRCUIT.
  
 6) FBC 107.2.1 SPECIFY THE CIRCUITS NUMBERS ON THE
 ELECTRICAL FLOOR PLAN IN COORDINATION WITH THE PANEL
 SCHEDULE.
  
  