Plan Review Notes
Plan Review Notes For Permit 15010449
Permit Number 15010449
Review Stop B
Sequence Number 1
Notes
Date Text
2015-02-05 08:26:28PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET S-2.0 SHOWS THAT THE ATTIC WILL BE USED
 STORAGE. FBC-R301.5 REQUIRES A 20 PSF LIVE LOAD FOR THE
 BOTTOM CORD OF TRUSSES USED FOR LIMITED STORAGE.
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. (1) SUBMIT THE INSTALLATION
 INSTRUCTIONS FOR SIMPSON HETAL 12 CONNECTOR. (2) NOA
 NO. 12-0209.13 THAT WAS SUBMITTED FOR THE 8" CAST -
 CRETE LINTELS WAS SUPERSEDED ON 10/9/2014 BY NOA NO.
 14-0903.02. SUBMIT THE CURRENT ONE.
  
  
  
  
  
  