Plan Review Notes For Permit 15010449 |
Permit Number |
15010449 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-02-05 08:26:28 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHEET S-2.0 SHOWS THAT THE ATTIC WILL BE USED | | STORAGE. FBC-R301.5 REQUIRES A 20 PSF LIVE LOAD FOR THE | | BOTTOM CORD OF TRUSSES USED FOR LIMITED STORAGE. | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. (1) SUBMIT THE INSTALLATION | | INSTRUCTIONS FOR SIMPSON HETAL 12 CONNECTOR. (2) NOA | | NO. 12-0209.13 THAT WAS SUBMITTED FOR THE 8" CAST - | | CRETE LINTELS WAS SUPERSEDED ON 10/9/2014 BY NOA NO. | | 14-0903.02. SUBMIT THE CURRENT ONE. | | | | | | | | | | | | |
|