Date |
Text |
2015-04-09 06:14:21 | 1) SHT. P.5.2 - THE RAINWATER RISER FOR THE SHOWROOM |
| AREA DOES NOT MATCH THE PLAN VIEW ON P2.1.1. ONE |
| SECTION SHOWS A WYE CONNECTION ABOVE GROUND AND THE |
| RISER SPLITTING INTO TWO HORIZONTAL BRANCES ON THE PLAN |
| VIEW ON P2.1.1 AND THE SAME SECTION IS SHOWN AS ONE |
| LINE RISING UP AND COLLECTING 4 ROOF DRAINS. CLARIFY. |
| 2) SHT. P2.1.2.- THERE ARE TWO 4" RAINWATER BRANCHES |
| THAT JUST END AND HAVE NO CONNECTION TO ROOF DRAINS OR |
| SHOW A NOTE DETAILING CONTINUATION POINTS. THESE LINES |
| ARE LOCATED IN THE PARTS AREA #135. I HAVE HIGHLIGHTED |
| AND CLOUDED THE AREA IN RED. ONE TERMINATES NEAR GRID |
| LINE G-2.2 AND THE OTHER IS BY GRID LINE F-1 BY STAIR |
| #2. CLARIFY. 2ND REQUEST. |
| 3) SHT.P2.1.3. - THE TRANSAIR ALUMINUM PIPE THAT IS |
| CALLED OUT ON THE PLAN IS SHOWN AS BEING INSTALLED |
| UNDERGROUND. I HAVE RESEARCHED THE PIPNG AND IT APPEARS |
| IT MAY ONLY BE APPROVED FOR ABOVE GROUND INSTALLATION. |
| SUBMIT VERIFICATION FROM THE MANUFACTURER THAT IT IS |
| APPROVED FOR UNDERGROUND INSTALLATION. THIS CAN BE A |
| DEFERRED SUBMITTA.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| 4) SHT. P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP |
| ABOVE CEILING BUT THERE IS NOTHING SHOWN. I HAVE |
| HIGHLIGHTED THE AREA OF ISSUE.THERE IS A NOTE THAT ALSO |
| STATES" SEE SHT. P2.1.2 FOR CONTINUATION" BUT NOTHING |
| IS SHOWN ON SHT. P2.1.2.CLARIFY. 2ND REQUEST. |
| 5) SHT.P2.1.2. - SHOWS A 3" RAINWATER LEADER IN STAIR |
| ENCLOSURE # 3 AND ALSO IN STAIR #1 . I HAVE REVIEWED |
| YOUR RESPONSE TO MY COMMENT. THE ARCHITECT OF RECORD |
| HAS RATED BOTH OF THESE ENTIRE ENCLOSURES AS ONE HOUR |
| ON SHT.A-001. THE RAINWATER PIPING CANNOT PENETRATE ANY |
| WALLS OF THESE RATED ENCLOSURES PER 2010 FBC 1022.4. |
| THIS CODE SECTION DOES NOT JUST APPLY TO ADJACENT |
| SPACES OR ENCLOSURES.IF THE 3" RAINWATER RISER ENTERS |
| THE ENCLOSURES FROM UNDERGROUND THROUGH THE GROUND |
| FLOOR SLAB OF THE ENCLOSURE, THEN THERE IS NOT AN ISSUE |
| BUT THAT IS NOT WHAT THE RAINWATER RISER ON SHT. P5.2 |
| DEPICTS OR THE PLAN VIEWS ON P2.1.1 OR P2.1.2. IF THIS |
| IS SUCH THE CASE, THEN CLEARLY IDENTIFY THIS ON BOTH |
| SHEETS. SHT. 5.2 SHOWS THIS 3" LINE CONNECTING TO THE |
| STORM DRAIN LINE BELOW THE ROOF SLAB, NOT UNDERGROUND. |
| CLARIFY. |
| |
| PLEASE CONTACT ME AT THE NUMBER BELOW TO SET UP AN |
| APPOINTMENT OR TO DISCUSS THE COMMENTS. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| 561-805-6692 |
| [email protected] |
| |