2015-03-25 15:24:50 | 1) SUBMIT A RISER DIAGRAM FOR THE RAINWATER SYSTEM.WPB |
| AMEND. TO 2010 FBC SEC. 107.3.5.1.3. |
| 2) SHT. P2.1.2 - THERE IS A 4" RAIN WATER LEADER IN THE |
| PARTS AREA 3 135 THAT TERMINATES NOWHERE. CLARIFY. |
| 3) SHT. P5.1 - SIZE THE VENT FOR THE HANDICAP WATER |
| CLOSET IN THE MEN'S RESTROOM # 112. |
| 4) THE 3" VTR'S FOR THE SHOWROOM AND SERVICE AREA |
| REDUCE FROM 3" TO 2" .CLARIFY. |
| 5) SHT.P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP |
| ABOVE CEILING BUT NOTHING IS SHOWN. CLARIFY. |
| 6) SHT. P2.1.2 - SHOWS A 4" RAINWATER LINE WITH NO |
| TERMINATION POINT AND ALSO SHOWS A 4" RAINWATER LEADER |
| WITH 870 SQ. FT. WITH NO TERMINATION POINT.SEE PARTS |
| AREA PLAN.CLARIFY. |
| 7) SUBMIT A CONDENSATE RISER DIAGRAM. SHOW ALL PIPE |
| SIZES. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| 8) SHT. P2.1.2 - THERE IS A CONDENSATE BRANCH NEAR THE |
| EXTERIOR WALL IN THE SERVICE ARE BY GRID LINE 5F THAT |
| GOES NOWHERE. CLARIFY. |
| 9) SUBMIT A REVISED RAINWATER RISER DIAGRAM THAT |
| CLEARLY REFLECTS ALL THE CHANGES TO THE STORWATER |
| PIPING SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3. |
| 10) SHT.P2.1.2 - SIZE THE CONDENSATE LINE EXITING THE |
| BUILDING . |
| 11) SHT.P2.1.3 - INDICATE THE TYPE OF PIPING BEING |
| UTILIZED FOR THE COMPRESSED AIR SYSTEM. PVC IS NOT |
| APPROVED TO BE USED FOR COMPRESSED AIR. |
| 12) SHT.P2.1.3 - THE UNDERGROUND COMPRESSED AIR AND THE |
| WATER LINES ARE NOT SHOWN CONTINUING ON SHT. P2.1.2. |
| CLARIFY. |
| 13) SHT. P2.1.3 - SHOWS A 1" COMPRESSED AIR LINE |
| ENTERING AN AREA THAT COULD BE THE COMRESSOR ROOM # |
| 143. IF SO, IDENTIFY THE LINE AS SUCH. |
| 14) SHT. P2.1.2 - LOCATION OF EYEWASH AT EQUIPMENT |
| STORAGE AREA # 145 SHOWN ON RISER DOES NOT CORRELATE |
| WITH THE RSANITARY TISER ON SHT.P5.1. |
| 15) SHT.P2.1.2 - SHOWS A 3" RAINWATER LEADER IN STAIR |
| ENCLOSURE # 3. PENETRATIONS INTO AND OPENINGS THROUGH |
| AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT AS PROVIDED IN |
| 2010 FBC SEC.1022.4. |
| 16) SUPPLY CONFIRMATION FROM SCHIER PRODUCTS THAT THE |
| OIL/SAND CALCULATIONS HAVE BEEN REVIEWED AND THAT THE |
| SIZE OF THE INTERCEPTOR IS SIZED PROPERLY.2010 FPC |
| SEC.1003.2. YOU CAN CONTACT LEE SCHNEEWEISS AT |
| 1-800-538-4792 & [email protected]. I HAVE CALCULATED |
| THE SQUARE FOOTAGE OF THIS AREA FROM SHT.A114 AND THE |
| RESULT I HAVE IS APPROXIMATELY 1900 SQ. FEET WHICH IS |
| HIHER THAN YOUR CALCULATIONS. |
| 17.) SUBMIT SPECIFICATIONS FOR THE AIR COMPRESSORS. WPB |
| AMEND. TO 2010 FBC SEC.107.2.1. |
| 18) SHT.P3.1.2 - THE NUMBER OF COMPRESSED AIR OULETS DO |
| NOT CORRELATE WITH SHT.P6.1. THERE ARE 2 ADDITIONAL |
| OUTLETS ON THE COMPRESSED AIR RISER. CLARIFY. |
| 19) SHT. P5.1 - THE HANDICAPPPED LAVATORY IN THE MEN'S |
| RESTROOM #141 IS NOT SHOWN ON THE SANITARY RISER. |
| CLARIFY. |
| 20) SHT. P6.1 - THE WATER RISER ON P6.1 DOES NOT |
| CORRELATE WITH SHT.P3.1.2. ( SERVICE AREA DOMESTIC |
| WATER PLAN ) CLARIFY. |
| 21) SHT.P6.1 - WATER RISER - THE NUMBER OF HOSE BIBBS, |
| THE LAYOUT OF THE HOSE BIBBS, WHERE THE WATER MAUN |
| ENTERS THE BUILDING DOES NOT SEEM TO CORRELATE WITH |
| SHT. P3.1.2. |
| 22) SHT. P6.1 SHOWS AN 1 1/2" LINE TO SK-2. IS THIS |
| CORRECT? |
| 23) SHT. P6.1 - THE WATER LINE GOES FROM 2 1/2" TO 2" |
| THEN BACK TO 2 1/2" AGAIN. CLARIFY. SEE AREA AT MEN'S |
| RESTROOM #112. |
| |
| PLUMBING PLAN REVIEW |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |