Plan Review Notes
Plan Review Notes For Permit 15010430
Permit Number 15010430
Review Stop P
Sequence Number 2
Notes
Date Text
2015-03-25 15:24:501) SUBMIT A RISER DIAGRAM FOR THE RAINWATER SYSTEM.WPB
 AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 2) SHT. P2.1.2 - THERE IS A 4" RAIN WATER LEADER IN THE
 PARTS AREA 3 135 THAT TERMINATES NOWHERE. CLARIFY.
 3) SHT. P5.1 - SIZE THE VENT FOR THE HANDICAP WATER
 CLOSET IN THE MEN'S RESTROOM # 112.
 4) THE 3" VTR'S FOR THE SHOWROOM AND SERVICE AREA
 REDUCE FROM 3" TO 2" .CLARIFY.
 5) SHT.P2.1.1 REFERS TO 1" CONDENSATE PIPE AND PUMP
 ABOVE CEILING BUT NOTHING IS SHOWN. CLARIFY.
 6) SHT. P2.1.2 - SHOWS A 4" RAINWATER LINE WITH NO
 TERMINATION POINT AND ALSO SHOWS A 4" RAINWATER LEADER
 WITH 870 SQ. FT. WITH NO TERMINATION POINT.SEE PARTS
 AREA PLAN.CLARIFY.
 7) SUBMIT A CONDENSATE RISER DIAGRAM. SHOW ALL PIPE
 SIZES. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 8) SHT. P2.1.2 - THERE IS A CONDENSATE BRANCH NEAR THE
 EXTERIOR WALL IN THE SERVICE ARE BY GRID LINE 5F THAT
 GOES NOWHERE. CLARIFY.
 9) SUBMIT A REVISED RAINWATER RISER DIAGRAM THAT
 CLEARLY REFLECTS ALL THE CHANGES TO THE STORWATER
 PIPING SYSTEM.WPB AMEND. TO 2010 FBC SEC.107.3.5.1.3.
 10) SHT.P2.1.2 - SIZE THE CONDENSATE LINE EXITING THE
 BUILDING .
 11) SHT.P2.1.3 - INDICATE THE TYPE OF PIPING BEING
 UTILIZED FOR THE COMPRESSED AIR SYSTEM. PVC IS NOT
 APPROVED TO BE USED FOR COMPRESSED AIR.
 12) SHT.P2.1.3 - THE UNDERGROUND COMPRESSED AIR AND THE
 WATER LINES ARE NOT SHOWN CONTINUING ON SHT. P2.1.2.
 CLARIFY.
 13) SHT. P2.1.3 - SHOWS A 1" COMPRESSED AIR LINE
 ENTERING AN AREA THAT COULD BE THE COMRESSOR ROOM #
 143. IF SO, IDENTIFY THE LINE AS SUCH.
 14) SHT. P2.1.2 - LOCATION OF EYEWASH AT EQUIPMENT
 STORAGE AREA # 145 SHOWN ON RISER DOES NOT CORRELATE
 WITH THE RSANITARY TISER ON SHT.P5.1.
 15) SHT.P2.1.2 - SHOWS A 3" RAINWATER LEADER IN STAIR
 ENCLOSURE # 3. PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT AS PROVIDED IN
 2010 FBC SEC.1022.4.
 16) SUPPLY CONFIRMATION FROM SCHIER PRODUCTS THAT THE
 OIL/SAND CALCULATIONS HAVE BEEN REVIEWED AND THAT THE
 SIZE OF THE INTERCEPTOR IS SIZED PROPERLY.2010 FPC
 SEC.1003.2. YOU CAN CONTACT LEE SCHNEEWEISS AT
 1-800-538-4792 & [email protected]. I HAVE CALCULATED
 THE SQUARE FOOTAGE OF THIS AREA FROM SHT.A114 AND THE
 RESULT I HAVE IS APPROXIMATELY 1900 SQ. FEET WHICH IS
 HIHER THAN YOUR CALCULATIONS.
 17.) SUBMIT SPECIFICATIONS FOR THE AIR COMPRESSORS. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 18) SHT.P3.1.2 - THE NUMBER OF COMPRESSED AIR OULETS DO
 NOT CORRELATE WITH SHT.P6.1. THERE ARE 2 ADDITIONAL
 OUTLETS ON THE COMPRESSED AIR RISER. CLARIFY.
 19) SHT. P5.1 - THE HANDICAPPPED LAVATORY IN THE MEN'S
 RESTROOM #141 IS NOT SHOWN ON THE SANITARY RISER.
 CLARIFY.
 20) SHT. P6.1 - THE WATER RISER ON P6.1 DOES NOT
 CORRELATE WITH SHT.P3.1.2. ( SERVICE AREA DOMESTIC
 WATER PLAN ) CLARIFY.
 21) SHT.P6.1 - WATER RISER - THE NUMBER OF HOSE BIBBS,
 THE LAYOUT OF THE HOSE BIBBS, WHERE THE WATER MAUN
 ENTERS THE BUILDING DOES NOT SEEM TO CORRELATE WITH
 SHT. P3.1.2.
 22) SHT. P6.1 SHOWS AN 1 1/2" LINE TO SK-2. IS THIS
 CORRECT?
 23) SHT. P6.1 - THE WATER LINE GOES FROM 2 1/2" TO 2"
 THEN BACK TO 2 1/2" AGAIN. CLARIFY. SEE AREA AT MEN'S
 RESTROOM #112.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  