2015-03-25 10:04:31 | 2/25/2015 |
| PROJECT: BRAMAN AUDI |
| PERMIT#: 14040379, REVISION #15010430 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION. |
| THE PLANS HAVE BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES PRIOR TO INSPECTION |
| WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT |
| OF RE-INSPECTION FEE(S). |
| |
| 1) SHEET E3.1.1 |
| A) NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE |
| PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER |
| PROTECTION. |
| B) NEC 110.3(B) PROVIDE EQUIPMENT SUBMITTALS ON |
| MOTORIZED BLINDS. VERIFY LISTING ON MOTORIZED BLINDS TO |
| VERIFY THEY ARE APPROVED FOR INSTALLATION AS SHOWN. |
| |
| 2) NEC 110.16 ADD NOTE: PROVIDE SAFETY LABELING FOR ARC |
| FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN |
| DISCONNECTING MEANS. |
| |
| 3) NEC 511.10. BATTERY CHARGING EQUIPMENT. BATTERY |
| CHARGERS AND THEIR CONTROL EQUIPMENT, AND BATTERIES |
| BEING CHARGED, SHALL NOT BE LOCATED WITHIN LOCATIONS |
| CLASSIFIED IN NEC 511.3. |
| |
| 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, FUEL DISPENSING, FIRE |
| ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, |
| AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |