Plan Review Notes
Plan Review Notes For Permit 15010430
Permit Number 15010430
Review Stop E
Sequence Number 2
Notes
Date Text
2015-03-25 10:04:312/25/2015
 PROJECT: BRAMAN AUDI
 PERMIT#: 14040379, REVISION #15010430
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION.
 THE PLANS HAVE BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES PRIOR TO INSPECTION
 WILL RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT
 OF RE-INSPECTION FEE(S).
  
 1) SHEET E3.1.1
 A) NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE
 PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER
 PROTECTION.
 B) NEC 110.3(B) PROVIDE EQUIPMENT SUBMITTALS ON
 MOTORIZED BLINDS. VERIFY LISTING ON MOTORIZED BLINDS TO
 VERIFY THEY ARE APPROVED FOR INSTALLATION AS SHOWN.
  
 2) NEC 110.16 ADD NOTE: PROVIDE SAFETY LABELING FOR ARC
 FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN
 DISCONNECTING MEANS.
  
 3) NEC 511.10. BATTERY CHARGING EQUIPMENT. BATTERY
 CHARGERS AND THEIR CONTROL EQUIPMENT, AND BATTERIES
 BEING CHARGED, SHALL NOT BE LOCATED WITHIN LOCATIONS
 CLASSIFIED IN NEC 511.3.
  
 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, FUEL DISPENSING, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  