Plan Review Notes
Plan Review Notes For Permit 15010430
Permit Number 15010430
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-29 06:10:331) TRENCH DRAINS SHALL COMPLY WITH ASME 112.6.3 PER THE
 2010 FL. PLBG. CODE SEC.412.1. SUBMIT DOCUMENTATION TO
 SHOW COMPLIANCE.
 2) SHT.P2.1.2. HAS ARROWS INDICATING AN UNDERGROUND
 STORM DRAIN BUT NO PIPING IS SHOWN ON THE PLAN.SUBMIT
 DRAWINGS THAT CLEARLY REFLECT THE PIPING AND THE SCOPE
 OF WORK TO BE DONE. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 3) THE CONDENSATE LINES ON THE PLAN ARE VERY LIGHT AND
 DIFFICULT TO READ. THESE WILL NOT SHOW WHEN THE PLANS
 ARE SCANNED FOR RECORD RETENTION. THE CONDENSATE LINES
 AND ALL OTHER PIPING ON THE PLUMBING PLANS SHALL BE
 CLEAR IN DETAIL AND LEGIBLE. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 4) SHT.P2.1.2. - SHOWS P-TRAPS ON CONDENSATE LINES BUT
 THE PLAN DOES NOT SHOW TO WHAT THEY ARE CONNECTED.
 CLARIFY.
 5) THERE ARE NOTES & ARROWS ALL OVER THE PLANS (
 P2.1.2, P2.1.3, P3.1.2) IDENTIFYING ITEMS BUT NOTHING
 IS SHOWN AT THE LOCATION,E.G. STORM DRAIN LINE, RAIN
 WATER LEADERS, 4" STORM DRAIN LINE, BFP DEVICE, 3" VENT
 BELOW GRADE, ETC. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P2.1.3 - CALLS OUT A 4" SANITARY LINE
 DISCHARGING INTO THE OIL/SAND SEPARATOR. WHAT
 DISCHARGES INTO THIS LINE? SANITARY LINES SHALL NOT
 DISCHARGE INTO THE SEPARATOR. WASTES THAT DO NOT
 REQUIRE TREATMENT OR SEPARATION SHALL NOT BE DISCHARGED
 INTO ANY INTERCEPTOR OR SEPARATOR. 2010 1003.2. PLANS
 REFER TO "BROADWAY EQUIPMENT PLANS." CLARIFY.
 7) INDICATE THE TYPE OF PIPE MATERIAL BEING USED FOR
 THE COMPRESSED AIR SYSTEM. PVC PIPING CANNOT BE USED
 FOR COMPRESSED AIR PER MANUFACTURER'S SPECIFICATIONS.
 FPC SEC.303.2
 8) SHT.P2.1.3 - CLEANOUTS SHALL BE INSTALLED IN THE
 TRENCH DRAIN SYSTEM PER THE 2010 FPC SEC. 708.
 9) CLEARLY IDENTIFY ALL PIPE LINES ON THE PLANS, AND
 SIZE ALL LINES. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 10) SHT.P5.1 - THERE ARE LINES INTO THE INTERCEPTOR
 THAT HAVE NO BEGINNING POINT ( 3" & 4" LINES). CLARIFY.
 11) SHT. P5.1 - A LAVATORY IN THE WOMEN'S RESTROOM IS
 MISSING FROM THE SANITARY RISER FOR THE SERVICE AREA..
 12) SHT. P6.1 - THE DOMESTIC WATER RISER IS SO LIGHT ON
 THE PLANS IT IS ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE
 DRAWINGS THE REFLECT THE SCOPE OF WORK.WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 13) SHT. P6.1 - THE COMPRESSED AIR RISER IS SO LIGHT ON
 THE PLANS IT IS ILLEGIBLE. SUBMIT CLEAR AND LEGIBLE
 DRAWINGS THE REFLECT THE SCOPE OF WORK.WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 14) SHT. P5.1 - THERE IS A LAVATORY MISSING ON THE
 SERVICE AREA SANITARY RISER.
 15) THE SANITARY PIPING FOR THE EMERGENCY
 EYEWASH/SHOWER ON THE RISER DOES NOT CORRELATE WITH THE
 FLOOR PLAN. CLARIFY.
 16) THE WASTE LINES SHOWN ON THE RISER BY THE OIL/SAND
 SEPARATOR ARE NOT SHOWN ON SHT. P2.1.2.CLARIFY.
 17) PLEASE ASSEMBLE THE PLANS INTO TWO COMPLETE SETS OF
 PLANS WITH THE SHEETS BOUND TOGETHER.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  