Date |
Text |
2015-02-03 14:32:27 | 2/3/2015 |
| PROJECT: BRAMAN AUDI |
| PERMIT#: 14040379, REVISION #15010430 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC, |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) SHEET E1.2 |
| NOTE 14 CALLS FOR A NEW WEATHERPROOF BOX AND EMPTY |
| CONDUIT WITH PULL STRING FOR CCTV CAMERAS. IF THE IDEA |
| HERE IS TO INSTALL CCTV CAMERAS ON THE LIGHT POLES, |
| PROVIDE A SEPARATE RACEWAY FOR THE CCTV CONDUCTORS IN |
| THE LIGHT POLE TO SEPARATE THEM FROM THE HIGH VOLTAGE |
| CONDUCTORS IN THE POLE FOR THE LIGHTS. |
| |
| 2) E2.1.1 |
| NEC 700.16 PROVIDE ADEQUATE EMERGENCY ILLUMINATION TO |
| EFFECTIVELY ILLUMINATE ALL MEANS OF EGRESS. |
| |
| 3) SHEET E3.1.1 |
| A) NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE |
| PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER |
| PROTECTION. |
| B) NEC 110.3(B) PROVIDE EQUIPMENT SUBMITTALS ON |
| MOTORIZED BLINDS |
| |
| 4) SHEET E4.1 |
| NEC 110.26 (C)(3) WHERE EQUIPMENT RATED 1200 A OR MORE |
| THAT CONTAINS OVERCURRENT DEVICES, SWITCHING DEVICES, |
| OR CONTROL DEVICES IS INSTALLED AND THERE IS A |
| PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS |
| FROM THE WORKING SPACE LESS THAN 25? FROM THE NEAREST |
| EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL OPEN IN |
| THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC |
| BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE |
| NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. |
| REVISE THE MOUTH ELECTRICAL ROOM DOOR TO BE EQUIPPED |
| WITH PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT |
| ARE NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE. |
| |
| 5) SHEET E6.1 |
| PANEL L1AA INDICATES A TOTAL CONNECTED LOAD OF 72.5 KVA |
| ON A 120/208V 3PHASE WYE 200AMP OCPD AND FEEDER. |
| 72.5KVA / 208V, 3PH (X1.732) IS JUST OVER 200AMP. |
| REVISE THE PANEL SCHEDULE AND LOADS ON THE PANEL TO |
| ALLEVIATE THE OVERLOAD CONDITION. |
| |
| 6) NEC 110.9 VERIFY THE ELECTRICAL SERVICE |
| DISCONNECTING MEANS HAS A FAULT CURRENT RATING THAT IS |
| SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT |
| THAT MUST BE INTERRUPTED. |
| |
| 7) NEC 110.16 ADD NOTE: ?PROVIDE SAFETY LABELING FOR |
| ARC FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN |
| DISCONNECTING MEANS.? |
| 8) NEC 511.10 BATTERY CHARGING EQUIPMENT. BATTERY |
| CHARGERS AND THEIR CONTROL EQUIPMENT, AND BATTERIES |
| BEING CHARGED, SHALL NOT BE LOCATED WITHIN LOCATIONS |
| CLASSIFIED IN NEC 511.3. |
| |
| 9) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, FUEL DISPENSING, FIRE |
| ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV, |
| AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |