Plan Review Notes
Plan Review Notes For Permit 15010430
Permit Number 15010430
Review Stop E
Sequence Number 1
Notes
Date Text
2015-02-03 14:32:272/3/2015
 PROJECT: BRAMAN AUDI
 PERMIT#: 14040379, REVISION #15010430
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC,
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) SHEET E1.2
 NOTE 14 CALLS FOR A NEW WEATHERPROOF BOX AND EMPTY
 CONDUIT WITH PULL STRING FOR CCTV CAMERAS. IF THE IDEA
 HERE IS TO INSTALL CCTV CAMERAS ON THE LIGHT POLES,
 PROVIDE A SEPARATE RACEWAY FOR THE CCTV CONDUCTORS IN
 THE LIGHT POLE TO SEPARATE THEM FROM THE HIGH VOLTAGE
 CONDUCTORS IN THE POLE FOR THE LIGHTS.
  
 2) E2.1.1
 NEC 700.16 PROVIDE ADEQUATE EMERGENCY ILLUMINATION TO
 EFFECTIVELY ILLUMINATE ALL MEANS OF EGRESS.
  
 3) SHEET E3.1.1
 A) NEC 422.52 ELECTRIC DRINKING FOUNTAINS SHALL BE
 PROTECTED WITH GROUND FAULT CIRCUIT INTERRUPTER
 PROTECTION.
 B) NEC 110.3(B) PROVIDE EQUIPMENT SUBMITTALS ON
 MOTORIZED BLINDS
  
 4) SHEET E4.1
 NEC 110.26 (C)(3) WHERE EQUIPMENT RATED 1200 A OR MORE
 THAT CONTAINS OVERCURRENT DEVICES, SWITCHING DEVICES,
 OR CONTROL DEVICES IS INSTALLED AND THERE IS A
 PERSONNEL DOOR(S) INTENDED FOR ENTRANCE TO AND EGRESS
 FROM THE WORKING SPACE LESS THAN 25? FROM THE NEAREST
 EDGE OF THE WORKING SPACE, THE DOOR(S) SHALL OPEN IN
 THE DIRECTION OF EGRESS AND BE EQUIPPED WITH PANIC
 BARS, PRESSURE PLATES, OR OTHER DEVICES THAT ARE
 NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE.
 REVISE THE MOUTH ELECTRICAL ROOM DOOR TO BE EQUIPPED
 WITH PANIC BARS, PRESSURE PLATES, OR OTHER DEVICES THAT
 ARE NORMALLY LATCHED BUT OPEN UNDER SIMPLE PRESSURE.
  
 5) SHEET E6.1
 PANEL L1AA INDICATES A TOTAL CONNECTED LOAD OF 72.5 KVA
 ON A 120/208V 3PHASE WYE 200AMP OCPD AND FEEDER.
 72.5KVA / 208V, 3PH (X1.732) IS JUST OVER 200AMP.
 REVISE THE PANEL SCHEDULE AND LOADS ON THE PANEL TO
 ALLEVIATE THE OVERLOAD CONDITION.
  
 6) NEC 110.9 VERIFY THE ELECTRICAL SERVICE
 DISCONNECTING MEANS HAS A FAULT CURRENT RATING THAT IS
 SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT
 THAT MUST BE INTERRUPTED.
  
 7) NEC 110.16 ADD NOTE: ?PROVIDE SAFETY LABELING FOR
 ARC FLASH PROTECTION FOR THE PANEL BOARDS AND MAIN
 DISCONNECTING MEANS.?
 8) NEC 511.10 BATTERY CHARGING EQUIPMENT. BATTERY
 CHARGERS AND THEIR CONTROL EQUIPMENT, AND BATTERIES
 BEING CHARGED, SHALL NOT BE LOCATED WITHIN LOCATIONS
 CLASSIFIED IN NEC 511.3.
  
 9) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, FUEL DISPENSING, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved