Plan Review Notes
Plan Review Notes For Permit 15010430
Permit Number 15010430
Review Stop B
Sequence Number 1
Notes
Date Text
2015-02-07 10:08:54BUILDING PLAN REVIEW
 REVISION: 15010430
 PERMIT: 14040379
 ADD: 2101 OKEECHOBEE BLVD.
 CONT: HEDRICK BROTHERS
 TEL: (561)568-8931
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
 1A) A-101 & A-121 DETAILS 2 & 3 SHEET A-122 SHOWS NEW
 CAR LIFTS, SHEET A-122 DETAIL 2 & 3 SHOW THESE LIFTS
 WITH A PIT, THERE HAS BEEN NO STRUCTURAL
 SHEETS IN THIS SUBMITTAL, NO DETAILS AS TO THE TYPE OF
 LIFT, TRACTION OR HYDROLIC ETC.
  
 1B) SHEET A-121 SHOWS THE FINISH FLOOR AS A FLOOR TILE,
 A OIL SEPARATOR WAS NOT RREQUIRED BECAUSE OF THE
 NON-ABSORBENT SURFACE OF THE TILE, THAT THE OILS AND
 GREASE WERE TO BE CLEANED UP, THIS SHEET DOES NOT
 INDICATE THE SURFACE FINISH OF THE AREA WALLS NOR
 FLOOR. PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B: 406.6.4 FLOOR SURFACE.
 REPAIR GARAGE FLOORS SHALL BE OF CONCRETE OR SIMILAR
 NONCOMBUSTIBLE AND NONABSORBENT MATERIALS.
 EXCEPTION: SLIP-RESISTANT, NONABSORBENT, INTERIOR FLOOR
 FINISHES HAVING A CRITICAL RADIANT FLUX NOT MORE THAN
 0.45 W/CM2, AS DETERMINED BY NFPA 253, SHALL BE
 PERMITTED.
  
  
  
  
 BUILDING PROVISO FROM ISSUED PLANS:
  
 1) THE DESIGNER OF RECORD WOULD LIKE TO DEFER THE
 PRODUCT APPROVALS AS A DEFERRED SUBMITTAL 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION107.3.4.2.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, RAINSCREEN PERFORATED CORRUGATED
 METAL PANEL SYSTEM
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) PRE-ENGINEERED A/C STANDS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676