Plan Review Notes
Plan Review Notes For Permit 15010404
Permit Number 15010404
Review Stop P
Sequence Number 1
Notes
Date Text
2015-01-26 10:43:051) ACCESSIBILITY SHALL BE DESIGNED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, ACCESSIBILITY VOLUME NOT THE
 FAIR HOUSING ACT AS NOTED PER THE 2010 FBC SEC.438.7.
 2) THE SHOWERS SHALL BE A MINIMUM OF 30 INCHES IN WIDTH
 PER THE FAC SEC.608.2.2.
 3)THE PLUMBING FIXTURES SHALL COMPLY WITH THE 2010 FAC
 FOR HEIGHTS, CLEAR FLOOR SPACE, KNEE AND TOE CLEARANCES
 PER FAC SECS.212,213,214,305,306,603,604,606,608, 609,
 611.
 4) SHOW ALL THE REQUIRED CLEAR FLOOR SPACES AT THE
 FIXTURES ON THE FLOOR PLAN.WPB AMEND TO 2010 FBC
 SEC.107.2.1.
 5) SUBMIT A COPY OF THE EXISTING FLOOR PLAN. WPB AMEND
 TO 2010 FBC SEC.107.2.1.
 6) INDICATE THE PREVIOUS OCCUPANCY ON THE PLANS AND
 INDICATE IF THIS IS OR IS NOT A CHANGE OF OCCUPANCY.WPB
 AMEND TO 2010 FBC SEC.107.2.1.
 7) SUBMIT A WATER RISER DIAGRAM FOR REVIEW.WPB AMEND TO
 2010 FBC SEC.107.2.1, 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  