Plan Review Notes
Plan Review Notes For Permit 15010404
Permit Number 15010404
Review Stop M
Sequence Number 1
Notes
Date Text
2015-03-07 15:35:01PLAN DENIED
 1) REFER TO SECTION 304.1 GENERAL PROVIDE CLOTHES DRYER
 MANUFACTURERS INSTALLATION INSTRUCTIONS WITH PLANS.
 2010 FBC (M)
 2) REFER TO SECTION 306 ACCESS FOR SERVICE. FOR MVD AVD
 AND SF-1 2010FBC (M)
 3) NO BOOSTER FAN FOR CLOTHES DRYER. PER WEST PALM
 BEACH
 FIRE DEPARTMENT
 4) REFER TO SECTION 502.2 EXHAUST DISCHARGE AND
 501.2.1 LOCATION OF EXHAUST OUTLETS 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676