2015-04-25 06:38:12 | BUILDING PLAN REVIEW |
| PERMIT: 15010402 |
| ADD: 255 EVERNIA ST # 1405 |
| CONT: BLUEWATER BUILDERS |
| TEL: (954)753-7233 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SAT. APRIL 25/ 2015 |
| ACTION: DENIED |
| |
| NOTICE!!!!!! WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| |
| NOTICE: SUBMIT TEST REPORTS TO THE DESIGNER OF RECORD |
| FOR REVIEW BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT. |
| |
| 1) 2ND REQUEST, SUPPLY THE ASTM E-90 TEST REPORT FOR |
| FLOOR INSULATION. SHEET A152 SHOWS AN EXISTING SINGLE |
| ENTRY, SHEET A201 SHOWS A NEW PORTION OF THE CORRIDOR, |
| A LOBBY AREA AND 2 NEW ENTRIES TO (2) NEW R2 UNITS. THE |
| PLANS INDICATE EITHER A WALL IDENTIFICATION TAG 1 OR 2. |
| SHEET A903 SHOWS BOTH WALLS AS 1 HOUR FIRE RATED WALLS, |
| BOTH DETAILS ARE MISSING COMPLIANCE WITH: |
| 2010 FBC-B 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 2) 2ND REQUEST, SUPPLY THE ASTM E-90 TEST REPORT FOR |
| FLOOR INSULATION. SHEET A152 NOTE # 3 INDICATES TO |
| REMOVE ALL FLOOR TILE AND GROUT. SHEET A202 SHOW NEW |
| FLOOR TILE BUT THERE IS NO NOTES ABOUT THE FLOOR |
| FINISHES. PLEAS PROVIDE COMPLIANCE WITH : |
| 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 3) 2ND REQUEST SUPPLY THE TEST REPORT FOR FLAME SPREAD. |
| 2010 FBC-B 603.2.EXCEPTION (2) INSULATION INSTALLED |
| BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 4) COMPLIED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |