Plan Review Notes
Plan Review Notes For Permit 15010402
Permit Number 15010402
Review Stop M
Sequence Number 1
Notes
Date Text
2015-03-07 13:31:36PLAN DENIED
 1) REFER TO SECTION 304.1 GENERAL
 PROVIDE A COPY OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS
 FOR THE CLOTHES DRYER 2010 FBC (M)
 2) SECTION 504.6.4.1 SPECIFIED LENGTH EXCEPTION PERMITS
 BOOSTER FANS . HOWEVER WEST PALM BEACH FIRE RESCUE
 DOES NOT. IN THE 5TH EDITION 2014 OF THE FLORIDA CODES
 THE EXCEPTION FOR CLOTHES DRYER BOOSTER FANS HAS BEEN
 DELETED.
 3) REFER TO SECTION 602.2.1 MATERIALS WITH IN PLENUM'S.
 2010 FBC (M) INCLUDING A/C CLOSET DOORS AND CONDENSATE
 LINES.
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR MASTER
 BEDROOM
 TO SMALL, BEDROOM 2,3 LOOK LIKE THEY ARE JUMPING IN TO
 EACH OTHER
  
 PLAN REVIEW BY HAROLD MOSER