2015-03-07 13:31:36 | PLAN DENIED | | 1) REFER TO SECTION 304.1 GENERAL | | PROVIDE A COPY OF THE MANUFACTURER'S INSTALLATION | | INSTRUCTIONS | | FOR THE CLOTHES DRYER 2010 FBC (M) | | 2) SECTION 504.6.4.1 SPECIFIED LENGTH EXCEPTION PERMITS | | BOOSTER FANS . HOWEVER WEST PALM BEACH FIRE RESCUE | | DOES NOT. IN THE 5TH EDITION 2014 OF THE FLORIDA CODES | | THE EXCEPTION FOR CLOTHES DRYER BOOSTER FANS HAS BEEN | | DELETED. | | 3) REFER TO SECTION 602.2.1 MATERIALS WITH IN PLENUM'S. | | 2010 FBC (M) INCLUDING A/C CLOSET DOORS AND CONDENSATE | | LINES. | | 4) REFER TO SECTION 601.4 BALANCED RETURN AIR MASTER | | BEDROOM | | TO SMALL, BEDROOM 2,3 LOOK LIKE THEY ARE JUMPING IN TO | | EACH OTHER | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|