2015-01-26 09:05:26 | BUILDING PLAN REVIEW |
| PERMIT: 15010402 |
| ADD: 255 EVERNIA ST # 1405 |
| CONT: BLUEWATER BUILDERS |
| TEL: (954)753-7233 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. JAN. 26/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET A152 SHOWS AN EXISTING SINGLE ENTRY, SHEET |
| A201 SHOWS A NEW PORTION OF THE CORRIDOR, A LOBBY AREA |
| AND 2 NEW ENTRIES TO (2) NEW R2 UNITS. THE PLANS |
| INDICATE EITHER A WALL IDENTIFICATION TAG 1 OR 2. SHEET |
| A903 SHOWS BOTH WALLS AS 1 HOUR FIRE RATED WALLS, BOTH |
| DETAILS ARE MISSING COMPLIANCE WITH: |
| 2010 FBC-B 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION |
| ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED |
| CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR |
| EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR |
| OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS. |
| THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT |
| ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT |
| FITTING TO THE FRAME AND SILL. |
| |
| 2) SHEET A152 NOTE # 3 INDICATES TO REMOVE ALL FLOOR |
| TILE AND GROUT. SHEET A202 SHOW NEW FLOOR TILE BUT |
| THERE IS NO NOTES ABOUT THE FLOOR FINISHES. PLEAS |
| PROVIDE COMPLIANCE WITH : |
| 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2010 FBC-B 603.2.EXCEPTION (2) INSULATION INSTALLED |
| BETWEEN A FINISHED FLOOR AND SOLID DECKING WITHOUT |
| INTERVENING AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME |
| SPREAD INDEX OF NOT MORE THAN 200. |
| |
| 3) SHEET A152 NOTE # 7 INDICATES REMOVE EXISTING |
| DRYWALL CEILING AND FRAMING. SHEET A301 SHOWS NEW G. W. |
| B. CEILINGS BUT THERE IS NO INFORMATION AS TO WHAT THE |
| NEW FRAMING MEMBERS ARE CONSTRUCTED FROM, SIZE, NOR |
| GAUGE OF MATERIAL, ALLOWABLE SPANS AND SPACING BETWEEN |
| FRAMING MEMBERS, ATTACHMENT TO THE CONCRETE DECK ABOVE |
| NOR THE THICKNESS OF THE NEW G. W. B. CEILINGS OR TYPE |
| OF WALL BOARD. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 8. STRUCTURAL REQUIREMENTS SHALL INCLUDE: CEILING |
| SYSTEMS. |
| |
| 2509.2 BASE FOR TILE. |
| GLASS MAT WATER-RESISTANT GYPSUM BACKING PANELS, |
| DISCRETE NONASBESTOS FIBER-CEMENT INTERIOR SUBSTRATE |
| SHEETS OR NONASBESTOS FIBER-MAT REINFORCED CEMENT |
| SUBSTRATE SHEETS IN COMPLIANCE WITH ASTM C 1178, C 1288 |
| OR C 1325 AND INSTALLED IN ACCORDANCE WITH MANUFACTURER |
| RECOMMENDATIONS SHALL BE USED AS A BASE FOR WALL TILE |
| IN TUB AND SHOWER AREAS AND WALL AND CEILING PANELS IN |
| SHOWER AREAS. WATER-RESISTANT GYPSUM BACKING BOARD |
| SHALL BE USED AS A BASE FOR TILE IN WATER CLOSET |
| COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE WITH |
| GA-216 OR ASTM C 840 AND MANUFACTURER RECOMMENDATIONS. |
| REGULAR GYPSUM WALLBOARD IS PERMITTED UNDER TILE OR |
| WALL PANELS IN OTHER WALL AND CEILING AREAS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C 840. |
| |
| 2509.3 LIMITATIONS. |
| WATER-RESISTANT GYPSUM BACKING BOARD SHALL NOT BE USED |
| IN THE FOLLOWING LOCATIONS: |
| 1. OVER A VAPOR RETARDER IN SHOWER OR BATHTUB |
| COMPARTMENTS. |
| 2. WHERE THERE WILL BE DIRECT EXPOSURE TO WATER OR IN |
| AREAS SUBJECT TO CONTINUOUS HIGH HUMIDITY. |
| 3. ON CEILINGS WHERE FRAME SPACING EXCEEDS 12 INCHES |
| (305 MM) O.C. FOR 1/2-INCH-THICK (12.7 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD AND MORE THAN 16 |
| INCHES (406 MM) O.C. FOR 5/8-INCH-THICK (15.9 MM) |
| WATER-RESISTANT GYPSUM BACKING BOARD. |
| |