Plan Review Notes
Plan Review Notes For Permit 15010400
Permit Number 15010400
Review Stop B
Sequence Number 2
Notes
Date Text
2015-04-25 06:31:41BUILDING PLAN REVIEW
 PERMIT: 15010400
 ADD: 255 EVERNIA ST # 1404
 CONT: BLUEWATER BUILDERS
 TEL: (954)753-7233
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. APRIL 25/ 2015
 ACTION: DENIED
  
 NOTICE!!!!!!WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 NOTICE: SUBMIT TEST REPORTS TO THE DESIGNER OF RECORD
 FOR REVIEW BEFORE SUBMITTAL TO THE BUILDING DEPARTMENT.
  
  
 1) 2ND REVIEW, PROVIDE ACTUAL TEST IN COMPLIANCE WITH
 ASTM E 90 FOR FLOOR INSULATION. SHEET A152 SHOWS AN
 EXISTING SINGLE ENTRY, SHEET A201 SHOWS A NEW PORTION
 OF THE CORRIDOR, A LOBBY AREA AND 2 NEW ENTRIES TO (2)
 NEW R2 UNITS. THE PLANS INDICATE EITHER A WALL
 IDENTIFICATION TAG 1 OR 2. SHEET A903 SHOWS BOTH WALLS
 AS 1 HOUR FIRE RATED WALLS, BOTH DETAILS ARE MISSING
 COMPLIANCE WITH:
 2010 FBC-B 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90. PENETRATIONS OR OPENINGS IN CONSTRUCTION
 ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES; RECESSED
 CABINETS; BATHTUBS; SOFFITS; OR HEATING, VENTILATING OR
 EXHAUST DUCTS SHALL BE SEALED, LINED, INSULATED OR
 OTHERWISE TREATED TO MAINTAIN THE REQUIRED RATINGS.
 THIS REQUIREMENT SHALL NOT APPLY TO DWELLING UNIT
 ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 2) 2ND REVIEW, PROVIDE ACTUAL TEST IN COMPLIANCE WITH
 ASTM E 90 FOR FLOOR INSULATION. SHEET A152 NOTE # 3
 INDICATES TO REMOVE ALL FLOOR TILE AND GROUT. SHEET
 A202 SHOW NEW FLOOR TILE BUT THERE IS NO NOTES ABOUT
 THE FLOOR FINISHES. PLEASE PROVIDE COMPLIANCE WITH :
 2010 FBC-B 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3) 2ND REVIEW, PROVIDE ACTUAL TEST IN COMPLIANCE WITH
 ASTM E 90 FOR FLOOR INSULATION. 2010 FBC-B
 603.2.EXCEPTION (2) INSULATION INSTALLED BETWEEN A
 FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 200.
  
 4) COMPLIED.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]