2015-03-07 14:16:16PLAN DENIED
 1) REFER TO SECTION304.1 GENERAL
 PROVIDE A COPY OF THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS
 FOR CLOTHES DRYER
 2) SECTION 504.6.4.1 SPECIFIED LENGTH EXCEPTION PERMITS
 DRYER BOOSTER FAN, HOWEVER CITY OF WEST PALM FIRE
 RESCUE DOES NOT.
 IN THE 5TH EDITION 2010 OF THE FLORIDA CODES THE
 EXCEPTION FOR
 CLOTHES DRYER BOOSTER FANS HAS BEEN DELETED
 3) REFER TO SECTION 602.2.1 MATERIALS WITHIN PLENUM'S.
 2010 FBC (M) INCLUDING A/C CLOSET DOORS AND CONDENSATE
 DRAIN LINE.
 4) REFER TO SECTION 601.4 BALANCED RETURN AIR MASTER
 BEDROOM
 TO SMALL, BEDROOM 2,3, LOOK LIKE THEY ARE JUMPING INTO
 EACH OTHER
  
 PLAN REVIEW BY HAROLD MOSER