2015-02-19 10:42:31 | 1/15/2015 |
| PROJECT: 308 ARLINGTON RD. DOCK PEDESTAL |
| PERMIT#: 15010385 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: APPROVED WITH EXCEPTION. |
| |
| THE INFORMATION AND DOCUMENTATION REQUESTED TO BE |
| PROVIDE TO THE INSPECTOR ON THE JOB FOR FINAL |
| INSPECTION AND SUBMITTED TO DEVELOPMENT SERVICES FOR |
| SCANNING INTO THE PERMIT FILE. |
| |
| 1) PROVIDE THE OCPD AND WIRE SIZE FOR "FUTURE BOAT |
| LIFT" ON THE PANEL SCHEDULE. |
| |
| 2) PROVIDE MANUFACTURER DOCUMENTATION ON THE PROPOSED |
| DOCK PEDESTAL TO INDICATE THE MINIMUM MANUFACTURER |
| RECOMMENDED CIRCUITRY REQUIRED AND COMPLIANCE WITH NEC |
| 110.3(B) LISTING WITH A NRTL |
| |
| ) THERE IS NO INDICATION OF THE EXISTING # 6 WIRE OR |
| THE NEW PEDESTAL. INDICATE THE LOCATION AND WIRING |
| METHOD FOR THE EXISTING #6 WIRE. INDICATE THE LOCATION |
| AND WIRING METHOD FOR THE NEW PEDESTAL. |
| |
| 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, |
| 668.001-668.006 FBC, WPB |
| AMENDMENTS 107.2.1. PLANS ARE STILL NOT SIGNED OR BEAR |
| THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR |
| THE DESIGN. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |
| |
| |
| |
| |
| |
| |