Plan Review Notes For Permit 15010342 |
Permit Number |
15010342 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-22 14:21:05 | THIS PLAN WAS REVIEWED AND FAILED BY ROY LINDOW. FIRE | | INSPECTOR WITH PETER LEDUC, FIRE MARSHAL, WITH THE | | FOLLOWING COMMENTS: | | | | PROVIDE LOCATIONS OF EXISTING DEVICES TO BE REMOVED. | | | | NOT TO SCALE. | | | | INDICATE IF DEVICES ARE CEILING OR WALL MOUNT. | | | | PLAN CALLS FOR HORN SMOKES. PROVIDE JUSTIFICATION OR | | MAKE CORRECTIONS. | | | | PROVIDE VERIFICATION THAT FIRE ALARM IS CONNECTED TO | | AND PROVIDES NOTIFICATION THROUGHOUT ENTIRE (CONNECTED) | | BUILDINGS. | | | | BATTERY CALCULATIONS SHOW ONLY 5 ADDITIONAL DEVICES AND | | DOES NOT MATCH SUBMITTED DRAWINGS. | | | | PLANETARIUM DOES NOT SHOW NOTIFICATION DEVICES. | | | | | | | | |
|