2015-01-22 14:21:05THIS PLAN WAS REVIEWED AND FAILED BY ROY LINDOW. FIRE
 INSPECTOR WITH PETER LEDUC, FIRE MARSHAL, WITH THE
 FOLLOWING COMMENTS:
  
 PROVIDE LOCATIONS OF EXISTING DEVICES TO BE REMOVED.
  
 NOT TO SCALE.
  
 INDICATE IF DEVICES ARE CEILING OR WALL MOUNT.
  
 PLAN CALLS FOR HORN SMOKES. PROVIDE JUSTIFICATION OR
 MAKE CORRECTIONS.
  
 PROVIDE VERIFICATION THAT FIRE ALARM IS CONNECTED TO
 AND PROVIDES NOTIFICATION THROUGHOUT ENTIRE (CONNECTED)
 BUILDINGS.
  
 BATTERY CALCULATIONS SHOW ONLY 5 ADDITIONAL DEVICES AND
 DOES NOT MATCH SUBMITTED DRAWINGS.
  
 PLANETARIUM DOES NOT SHOW NOTIFICATION DEVICES.
  
  
  
  