Plan Review Notes For Permit 15010290 |
Permit Number |
15010290 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-01-20 10:51:37 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | NO REFERENCE IS MADE INDICATING THE TYPE OF EXISTING | | BUILDING OR EXISTING LIFE SAFETY FEATURES. | | | | NO REFERENCE IS MADE INDICATING THE FIRE RATING OF THE | | NEW WALL OR THE RATING OF THE PROPOSED WINDOWS. BASED | | ON THE EXISTING LIFE SAFETY FEATURES AND 1 OR 2 HOUR | | FIRE RATING IS REQUIRED. | | | | A DOOR SCHEDULE IS NOT INDICATED. | | | | A LIFE SAFETY PLAN IS NOT INCLUDED. A LIFE SAFETY PLAN | | SHALL BE SUBMITTED WITH DIMENSIONS INCLUDING OCCUPANY | | LOADS, PATH OF TRAVEL, EXIT LIGHTS, EMERGENCY LIGHTS, | | FIRE EXTINGUISHERS. EXITING THROUGH A WAREHOUSE, LESSER | | HAZARD TO GREATER HAZARD, MAY BE ALLOWED UNDER CERTAIN | | CONDITIONS, PLEASE REVIEW AND ENSURE IT IS ALLOWED IN | | THIS PROPOSED INSTALLATION. | | | | A FLOOR PLAN OF THE WAREHOUSE SHALL BE INCLUDED THAT | | INCLUDES PROPOSED PALLETS, RACKS, EQUIPMENT, COMMODITY | | STORED, ETC, IF APPLICABLE. | | | | |
|