Notes
Date Text
2015-01-20 10:51:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 NO REFERENCE IS MADE INDICATING THE TYPE OF EXISTING
 BUILDING OR EXISTING LIFE SAFETY FEATURES.
  
 NO REFERENCE IS MADE INDICATING THE FIRE RATING OF THE
 NEW WALL OR THE RATING OF THE PROPOSED WINDOWS. BASED
 ON THE EXISTING LIFE SAFETY FEATURES AND 1 OR 2 HOUR
 FIRE RATING IS REQUIRED.
  
 A DOOR SCHEDULE IS NOT INDICATED.
  
 A LIFE SAFETY PLAN IS NOT INCLUDED. A LIFE SAFETY PLAN
 SHALL BE SUBMITTED WITH DIMENSIONS INCLUDING OCCUPANY
 LOADS, PATH OF TRAVEL, EXIT LIGHTS, EMERGENCY LIGHTS,
 FIRE EXTINGUISHERS. EXITING THROUGH A WAREHOUSE, LESSER
 HAZARD TO GREATER HAZARD, MAY BE ALLOWED UNDER CERTAIN
 CONDITIONS, PLEASE REVIEW AND ENSURE IT IS ALLOWED IN
 THIS PROPOSED INSTALLATION.
  
 A FLOOR PLAN OF THE WAREHOUSE SHALL BE INCLUDED THAT
 INCLUDES PROPOSED PALLETS, RACKS, EQUIPMENT, COMMODITY
 STORED, ETC, IF APPLICABLE.
  
  