Plan Review Notes
Plan Review Notes For Permit 15010290
Permit Number 15010290
Review Stop B
Sequence Number 1
Notes
Date Text
2015-01-23 15:23:38BUILDING PLAN REVIEW
 PERMIT: 15010290
 ADD: 1640 CLARE AVE.
 CONT: THE WEITZ CO.
 TEL: (561)684-4807
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 23/ 2015
 ACTION: DENIED
  
 1) SHEET A101; MISSING CRITERIA FOR COMMERCIAL BUILDING
 PLAN REVIEW:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION:
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 1.1) TYPE OF OCCUPANCY
 1.2) MINIMUM BUILDING TYPE
 1.3) FIRE SPRINKLERED OR NOT?
 1.4) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS PROVIDE A LIFE SAFETY PLAN SHOWING ALL
 RACK STORAGE, IS THIS HIGH RACK STORAGE
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 2) SHEET A102 SHOWS A NEW OFFICE ENCLOSURE, IT APPEARS
 TO BE AN ACCESSORY OCCUPANCY <10% OF THE FLOOR AREA :
 2.1 THE PLANS DO NOT INDICATE THE WALL TYPE OF
 CONSTRUCTION, IF THERE IS TO BE A CEILING, HOW THE
 CEILING IS TO BE HUNG NOR IF THERE IS GOING TO BE
 CEILING JIOST? IS THERE TO BE STORAGE ABOVE THE OFFICE
 AREA, MEZZANINE? 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) THE PLANS DO NOT INDICATE IF THERE IS TO BE
 MECHANICAL VENTILATION, PLEASE PROVIDE COMPLIANCE WITH
 2010 FBC-B 1203.1 GENERAL.
 BUILDINGS SHALL BE PROVIDED WITH NATURAL VENTILATION IN
 ACCORDANCE WITH SECTION 1203.4, OR MECHANICAL
 VENTILATION IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL.
  
 4A) IF HIS SPACE IS TO BE AIR CONDITIONED PLEASE
 PROVIDE INSULATION IN ACCORDANCE WITH THE FL. ENERGY
 CODE. FBC-ENERGY 502.2.2.1.1 ABOVE-GRADE WALLS.
 THE MINIMUM THERMAL RESISTANCE (R-VALUE) OF THE
 INSULATING MATERIAL(S) INSTALLED IN THE WALL CAVITY
 BETWEEN THE FRAMING MEMBERS AND CONTINUOUSLY ON THE
 WALLS SHALL BE AS SPECIFIED IN TABLE 502.1.1.1(1) OR
 TABLE 502.1.1.1(2), BASED ON FRAMING TYPE AND
 CONSTRUCTION MATERIALS USED IN THE WALL ASSEMBLY. THE
 R-VALUE OF INTEGRAL INSULATION INSTALLED IN CONCRETE
 MASONRY UNITS (CMU) SHALL NOT BE USED IN DETERMINING
 COMPLIANCE WITH TABLE 502.1.1.1(1) OR TABLE
 502.1.1.1(2).
  
 4B) 502.2.1.2 CEILING INSULATION. INSULATION INSTALLED
 ON A SUSPENDED CEILING WITH REMOVABLE CEILING TILES
 SHALL NOT BE CONSIDERED PART OF THE MINIMUM THERMAL
 RESISTANCE OF THE ROOF INSULATION UNLESS THE
 ROOF/CEILING CAVITY IS SEALED FROM THE EXTERIOR
 ENVIRONMENT.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved