Date |
Text |
2015-01-23 15:23:38 | BUILDING PLAN REVIEW |
| PERMIT: 15010290 |
| ADD: 1640 CLARE AVE. |
| CONT: THE WEITZ CO. |
| TEL: (561)684-4807 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JAN. 23/ 2015 |
| ACTION: DENIED |
| |
| 1) SHEET A101; MISSING CRITERIA FOR COMMERCIAL BUILDING |
| PLAN REVIEW: |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION: |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| 1.1) TYPE OF OCCUPANCY |
| 1.2) MINIMUM BUILDING TYPE |
| 1.3) FIRE SPRINKLERED OR NOT? |
| 1.4) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS PROVIDE A LIFE SAFETY PLAN SHOWING ALL |
| RACK STORAGE, IS THIS HIGH RACK STORAGE |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| 2) SHEET A102 SHOWS A NEW OFFICE ENCLOSURE, IT APPEARS |
| TO BE AN ACCESSORY OCCUPANCY <10% OF THE FLOOR AREA : |
| 2.1 THE PLANS DO NOT INDICATE THE WALL TYPE OF |
| CONSTRUCTION, IF THERE IS TO BE A CEILING, HOW THE |
| CEILING IS TO BE HUNG NOR IF THERE IS GOING TO BE |
| CEILING JIOST? IS THERE TO BE STORAGE ABOVE THE OFFICE |
| AREA, MEZZANINE? 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 3) THE PLANS DO NOT INDICATE IF THERE IS TO BE |
| MECHANICAL VENTILATION, PLEASE PROVIDE COMPLIANCE WITH |
| 2010 FBC-B 1203.1 GENERAL. |
| BUILDINGS SHALL BE PROVIDED WITH NATURAL VENTILATION IN |
| ACCORDANCE WITH SECTION 1203.4, OR MECHANICAL |
| VENTILATION IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, MECHANICAL. |
| |
| 4A) IF HIS SPACE IS TO BE AIR CONDITIONED PLEASE |
| PROVIDE INSULATION IN ACCORDANCE WITH THE FL. ENERGY |
| CODE. FBC-ENERGY 502.2.2.1.1 ABOVE-GRADE WALLS. |
| THE MINIMUM THERMAL RESISTANCE (R-VALUE) OF THE |
| INSULATING MATERIAL(S) INSTALLED IN THE WALL CAVITY |
| BETWEEN THE FRAMING MEMBERS AND CONTINUOUSLY ON THE |
| WALLS SHALL BE AS SPECIFIED IN TABLE 502.1.1.1(1) OR |
| TABLE 502.1.1.1(2), BASED ON FRAMING TYPE AND |
| CONSTRUCTION MATERIALS USED IN THE WALL ASSEMBLY. THE |
| R-VALUE OF INTEGRAL INSULATION INSTALLED IN CONCRETE |
| MASONRY UNITS (CMU) SHALL NOT BE USED IN DETERMINING |
| COMPLIANCE WITH TABLE 502.1.1.1(1) OR TABLE |
| 502.1.1.1(2). |
| |
| 4B) 502.2.1.2 CEILING INSULATION. INSULATION INSTALLED |
| ON A SUSPENDED CEILING WITH REMOVABLE CEILING TILES |
| SHALL NOT BE CONSIDERED PART OF THE MINIMUM THERMAL |
| RESISTANCE OF THE ROOF INSULATION UNLESS THE |
| ROOF/CEILING CAVITY IS SEALED FROM THE EXTERIOR |
| ENVIRONMENT. |
| |
| 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |