2015-02-26 13:22:308100 IBIS BOULEVARD
 PERMIT #15010285
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4'-0" TO THE BACKSIDE OF THE STEAMER CAP.
  
 PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL
 BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  